Pump
A pump is to run at six different speeds, determined by
shifting between the preset references.
Switch no.:
1
3
4
0
0
0
Preset reference 1
0
0
1
Preset reference 2
0
1
0
Preset reference 3
0
1
1
Preset reference 4
1
0
0
Preset reference 5
1
0
1
Preset reference 6
When switch 1 is active, a setup change to setup 2 is
made.
Start/stop by means of switch 2
1.
Choice of Setup, lsb
2.
Start/stop
3.
Preset reference, lsb
4.
Preset reference, msb
The following must be programmed in order shown:
Function:
Parameter:
Setting:
Data value:
Active Setup
004
Multi-Setup
[5]
Digital input, term. 16
300
Choice of Setup, lsb
[10]
Digital input, term. 32
306
Preset reference, lsb
[6]
Digital input, term. 33
307
Preset reference, msb
[6]
Setup copying
006
Copy to Setup 2 from #
[2]
Edit Setup
005
Setup 1
[1]
Maximum reference
205
60
Preset reference 1
215
10%
Preset reference 2
216
20%
Preset reference 3
217
30%
Preset reference 4
218
40%
Edit Setup
005
Setup 2
[2]
Maximum reference
205
60
Preset reference 5
215
70%
Preset reference 6
216
100%
All other settings are based on factory settings. However, motor data (nameplate data) must always be entered in parameters 102-106.
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark
101
Con
nectio
n
e
x
ampl
e