Compact, Mains supply 3 x 525 - 600 V
According to international requirements
VLT type 5032
5042
5052
5062
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
43
54
65
81
I
VLT, MAX
(60 s) [A] (550 V)
47
59
72
89
I
VLT,N
[A] (575 V)
41
52
62
77
I
VLT, MAX
(60 s) [A] (575 V)
45
57
68
85
Output
S
VLT,N
[kVA] (550 V)
41
51
62
77
S
VLT,N
[kVA] (575 V)
41
52
62
77
Typical shaft output
P
VLT,N
[kW]
30
37
45
55
Typical shaft output
P
VLT,N
[HP]
40
50
60
75
High overload torque (160 %):
Output current
I
VLT,N
[A] (550 V)
34
43
54
65
I
VLT, MAX
(60 s) [A] (550 V)
54
69
86
104
I
VLT,N
[A] (575 V)
32
41
52
62
I
VLT, MAX
(60 s) [A] (575 V)
51
66
83
99
Output
S
VLT,N
[kVA] (550 V)
32
41
51
62
S
VLT,N
[kVA] (575 V)
32
41
52
62
Typical shaft output
P
VLT,N
[kW]
22
30
37
45
Typical shaft output
P
VLT,N
[HP]
30
40
50
60
Max. cable cross-section to motor,
35
50
50
50
brake and loadsharing [mm
2
]/[AWG]
2)
5)
2
1/0
1/0
1/0
Min. cable cross-section to motor,
10
16
16
16
brake and loadsharing [mm
2
]/[AWG]
4)
8
6
6
6
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
42
53
63
79
I
L,N
[A] (600 V)
38
49
58
72
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V)
33
42
53
63
I
L,N
[A] (600 V)
30
38
49
58
Max. cable cross-section
35
50
50
50
power[mm
2
]/[AWG]
2) 5)
2
1/0
1/0
1/0
Max. pre-fuses
[-]/UL
1)
[A]
60
75
90
100
Efficiency
3)
0.96
0.96
0.96
0.96
Weight IP 20 EB
[kg]
30
48
48
48
Power loss at max. load
[W]
1074
1362
1624
2016
Enclosure
IP 20 / Nema 1
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.