![background image](http://html1.mh-extra.com/html/danfoss/vlt-5000-series/vlt-5000-series_design-manual_3452348041.webp)
Bookstyle and Compact, Mains supply 3 x 380 - 500 V
According to international requirements
VLT type 5001
5002
5003
5004
Output current
I
VLT,N
[A] (380-415 V)
2.2
2.8
4.1
5.6
I
VLT, MAX
(60 s) [A] (380-415 V)
3.5
4.5
6.5
9
I
VLT,N
[A] (440-500 V)
1.9
2.6
3.4
4.8
I
VLT, MAX
(60 s) [A] (440-500 V)
3
4.2
5.5
7.7
Output
S
VLT,N
[kVA] (380-415 V)
1.7
2.1
3.1
4.3
S
VLT,N
[kVA] (440-500 V)
1.6
2.3
2.9
4.2
Typical shaft output
P
VLT,N
[kW]
0.75
1.1
1.5
2.2
Typical shaft output
P
VLT,N
[HP]
1
1.5
2
3
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10
4/10
4/10
4/10
Rated input current
I
L,N
[A] (380 V)
2.3
2.6
3.8
5.3
I
L,N
[A] (460 V)
1.9
2.5
3.4
4.8
Max. cable cross-section, power [mm
2
]/[AWG]
2)
4/10
4/10
4/10
4/10
Max. pre-fuses [-]/UL
1)
[A]
16/6
16/6
16/10
16/10
Efficiency
3)
0.96
0.96
0.96
0.96
Weight IP 20 EB Bookstyle [kg]
7
7
7
7.5
Weight IP 20 EB Compact [kg]
8
8
8
8.5
Weight IP 54 Compact [kg]
11.5
11.5
11.5
12
Power loss at max. load
[W]
55
67
92
110
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Design Guide
40
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark