Instructions
6 | AN37261897352601-010301 - 118A2177C
© Danfoss | Climate Solutions | 2022.02
and electrical connections.
•
Micro channel heat exchanger surface
adequately cleaned to avoid clogging.
The condenser must be checked at least once a year
for clogging and be cleaned if deemed necessary.
Access to the internal side of the condenser takes
place through the fan door. Microchannel coils
tend to accumulate dirt on the surface rather than
inside, which makes them easier to clean than fin-
&-tube coils.
• Switch off the power supply to the condensing
unit by turning off the main switch before
opening the fan panel.
• All electrical equipments, PPEs, tool must be
compatible and approved to use with A2L
refrigerants like R454C, R455A & R1234yf.
• Remove surface dirt, leaves, fibres, etc. with a
vacuum cleaner, equipped with a brush or other
soft attachment. Alternatively, blow compressed
air through the coil from the inside out, and
brush with a soft bristle. Do not use a wire brush.
Do not impact or scrape the coil with the vacuum
tube or air nozzle.
• Check if openings in partition panel and base
plate are free for pre-ventilation.
• Before closing the fan door, turn the fan blade
in a safe position, to avoid that the door hits the
fan.
If the refrigerant system has been opened, the
system has to be flushed with dry air or nitrogen
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to
be done, it shall be done in such a way that no
refrigerant can escape to the environment.
1
2
3
4
1. Valve inlet
2. Valve outlet
3. HP switch (Schrader port)
4. Service port
• Valve Fully Closed (Valve spindle entirely turned
clockwise)
- 1,3 and 4 Connected
- 2 has not connection to other ports
• Valve opened some turns (valve spindle somwher
between open & close)
- 1,2, 3 and 4 Connected
- Valve Fully Opened (Valve spindle entirely turned
anti clockwise)
- 1,2 and 3 Connected
- 4 has no connection to other ports
16 – Declaration of incorporation
•
Pressure Equipment Directive 2014/68/EU
EN 378-2:2016
- Refrigerating systems and Heat
Pumps - Safety and environmental requirements-
Parts 2: Design, construction, testing, marking and
documentation.
Low Voltage Directive 2014/35/EU
EN 60335-
1:2012 + A11:2014- Household and similar
electrical appliances-Safety-Part
1: General requirements-for all below mentioned
condensing units.
Eco-design DIRECTIVE 2009/125/ EC
,
establishing a framework for the setting of Eco-
design requirements for energy-related products.
REGULATION (EU) 2015/1095, implementing Eco-
design Directive 2009/125/EC with regard to Eco-
design requirements for professional refrigerated
storage cabinets, blast cabinets, condensing units
and process Chiller.
• Condensing unit measurements are made
according to standard “EN 13771-2:2017” –
Compressor and condensing units for refrigeration-
performance testing and test methods- part 2:
Condensing units. Eco design declaration; refer
Danfoss Coolselector®2 with code number (114X....)
to find the declaration.
17 - Warranty
Always transmit the model number and serial
number with any claim filed regarding this product.
The product warranty may be invalied in following
cases:
• Absence of nameplate.
•
External modifications, in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved by
Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or
maintenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model and serial number transmitted with
the warranty claim.
18 – Disposal
Only for Norway
Danfoss recommends that condensing
units and oil should be recycled by a
suitable company at its site.