![background image](http://html1.mh-extra.com/html/danfoss/ecl-2000/ecl-2000_installation-manual_3464574093.webp)
Application 11
EI.65.D4.02
87
Output Type 1
Name
Pin
Neutral
Description
P1
18
13
Circulation pump, heat circuit 1
P2
19
13
Appl. 11A: Circulation pump, heat circuit 2
Appl. 11B: Circulation pump, heat circuit 2 and charging
pump, hot-water circuit
P3
20
13
Appl. 11A: Charging pump, hot-water circuit
Appl. 11B: Changeover valve directing flow to the heat or
hot-water circuit
M1
16, 17
13
Motor valve on primary side of heat circuit 1
16: Close. 17: Open
M2
23, 24
13
Motor valve on primary side of heat exchanger supplying
heat circuit 2 and hot-water circuit
23: Close. 24: Open