Configuring the ECL 2000
EI.65.D4.02
32
Example 2
A flow meter yields 1 pulse for each 10 l of flow. The maximum flow is 100 l/s =
360 m
3
/h. Scaling and Interval are set as follows:
•
Scaling = 0.01 m
3
•
Interval = 60 s.
Example 3
A flow meter yields 1 pulse for each 1 l of flow. The maximum flow is 0.2 l/s =
720 l /h (which is less than 1024). Scaling and Interval will be set as follows:
•
Scaling = 1.00 l
•
Interval = 60 s.
Note:
To set Scaling to 1.00 l (flow measurement), decrease Scaling from 0.001 m
3
to
0.999 l, then increase the setting to 1.0 l.
Example 4
An energy meter yields 1 pulse for each kWh of energy consumption. The maxi-
mum power measurement is 1000 kW (which is less than 1024). Scaling and In-
terval will be set as follows:
•
Scaling = 1 kWh
•
Interval = 60 s.
Example 5
An energy meter yields 1 pulse for each 10 kWh of energy consumption. The
maximum power measurement is 2000 kW (which is greater than 1024). Scaling
and Interval will be set as follows:
•
Scaling = 0.01 MWh
•
Interval = 60 s.
Note:
To set Scaling to 0.01 MWh (energy measurement), increase Scaling from 1 kWh
to 0.1 MWh, then decrease the setting to 0.01 MWh.
Summary of Contents for ECL 2000
Page 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Page 2: ......
Page 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Page 16: ...Mounting EI 65 D4 02 10...
Page 26: ...Electrical Connections EI 65 D4 02 20...
Page 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Page 134: ...Appendix C Service Menus EI 65 D4 02 128...
Page 136: ...References EI 65 D4 02 130...
Page 140: ...Index EI 65 D4 02 134...