Configuring the ECL 2000
EI.65.D4.02
29
Sensor
Amplific.
range
Amplific.
default
Unit
Offset
range
Energy
0.00
–
9.99
10.0
–
99.9
10
kW
(per V)
± 0.00 – 9.99
± 10.0 – 100.0
0.10
–
9.99
10.0
–
99.9
MW
(per V)
Other
1
–
0
Example 1
A flow meter yields a voltage of 0 V at zero flow and 5 V at 10 m
3
/h. In this case,
Amplific. and Offset are set as follows:
•
Amplific. = 2 m
3
/h (per V)
•
Offset = 0.
Example 2
A sun intensity meter yields a voltage of 2 V when no light at all is present. The
voltage is 10 V when the meter detects a sun intensity of 40 W/m
2
. Amplific. and
Offset are set as follows:
•
Amplific. = 5 W/m
2
(per V)
•
Offset = – 10 W/m
2
.