Application 16, Type 2 Only
EI.65.D4.02
106
6.3.17 Application 16, Type 2 Only
System diagram 16A
Two separate heat circuits. Hot-water circuit with indirect control via heat ex-
changer.
Note:
ECL 2000 Type 2 must be used to control this application.
Heat circuit 1
The motor valve M1 controls the flow temperature, which is measured by the sen-
sor S1. The return temperature measured by the sensor S2 can be limited. The cir-
culation pump P1 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Heat circuit 2
The motor valve M2 controls the flow temperature, which is measured by the sen-
sor S4. The return temperature measured by the sensor S5 can be limited. The cir-
culation pump P2 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Hot-water circuit
The motor valve M3 controls the hot-water temperature, which is measured by the
sensor S10. The return temperature measured by the sensor S11 can be limited.
The circulation pump P3 is controlled according to the ECL 2000’s 7-day program
and the hot-water temperature (the pump is active when the reference hot-water
temperature is above 20 °C).
Summary of Contents for ECL 2000
Page 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Page 2: ......
Page 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Page 16: ...Mounting EI 65 D4 02 10...
Page 26: ...Electrical Connections EI 65 D4 02 20...
Page 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Page 134: ...Appendix C Service Menus EI 65 D4 02 128...
Page 136: ...References EI 65 D4 02 130...
Page 140: ...Index EI 65 D4 02 134...