Application 4
EI.65.D4.02
54
Wiring Type 1/230 V
Wiring Type 1/24 V
Input Type 1
Name
Pin
Common
Description
S1
3
12
Water temperature on secondary side of common heat ex-
changer. Must be connected
S2
4
12
Return temperature on primary side of common heat ex-
changer
S3
5
12
Outdoor temperature. Must be connected
S4
6
12
Flow temperature, heat circuit. Must be connected
S5
7
12
Optional: Can be installed to measure return temperature in
the heat circuit. If it is not installed, S2 measures the return
temperature
S6
8
12
Hot-water temperature. Must be connected
S7
9
12
Optional: Can be installed to measure lower tank tempera-
ture
S8
10
12
Default: Room temperature. Can be redefined
S9
11
12
Available
Summary of Contents for ECL 2000
Page 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Page 2: ......
Page 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Page 16: ...Mounting EI 65 D4 02 10...
Page 26: ...Electrical Connections EI 65 D4 02 20...
Page 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Page 134: ...Appendix C Service Menus EI 65 D4 02 128...
Page 136: ...References EI 65 D4 02 130...
Page 140: ...Index EI 65 D4 02 134...