![background image](http://html1.mh-extra.com/html/danfoss/ecl-2000/ecl-2000_installation-manual_3464574071.webp)
Application 6
EI.65.D4.02
65
Wiring Type 2
Input Type 2
Name
Pin
Common
Description
S1
3
12
Flow temperature, heat circuit. Must be connected
S2
4
12
Return temperature
S3
5
12
Outdoor temperature. Must be connected
S5
7
12
Charging temperature, hot-water circuit
S6
8
12
Upper storage tank temperature. Must be connected
S7
9
12
Lower storage tank temperature. Must be connected
S8
10
12
Default: Room temperature. Can be redefined
S9
11
12
Available
S10
23
12
Available
S11
24
12
Available
Output Type 2
Name
Pin
Neutral
Description
P1
16
13
Circulation pump, heat circuit
P2
17
13
Appl. 6A: Pump on primary side of heat exchanger in hot-
water circuit
Appl. 6B: Changeover valve directing flow to heat or hot-
water circuit
P3
18
13
Charging pump, hot-water circuit
M1
19
12
Motor valve on primary side of common heat exchanger
Note:
P4, the circulation pump of the hot-water circuit is not controlled by the ECL
2000.
Summary of Contents for ECL 2000
Page 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Page 2: ......
Page 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Page 16: ...Mounting EI 65 D4 02 10...
Page 26: ...Electrical Connections EI 65 D4 02 20...
Page 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Page 134: ...Appendix C Service Menus EI 65 D4 02 128...
Page 136: ...References EI 65 D4 02 130...
Page 140: ...Index EI 65 D4 02 134...