Application 13
EI.65.D4.02
95
Wiring Type 1/230 V
Wiring Type 1/24 V
Input Type 1
Name
Pin
Common
Description
S1
3
12
Water temperature on secondary side of common heat ex-
changer. Flow temperature, heat circuit 1. Must be con-
nected
S2
4
12
Return temperature, heat circuits 1 and 2
S3
5
12
Outdoor temperature. Must be connected
S4
6
12
Flow temperature, heat circuit 2. Must be connected
S5
7
12
Return temperature, heat circuit 2
S6
8
12
Hot-water temperature. Must be connected
S7
9
12
Optional: Can be installed to measure lower storage tank
temperature
S8
10
12
Default: Room temperature, heat circuit 1. Can be rede-
fined
S9
11
12
Default: Room temperature, heat circuit 2. Can be rede-
fined