Application 5
EI.65.D4.02
59
Wiring Type 1/230 V
Wiring Type 1/24 V
Input Type 1
Name
Pin
Common
Description
S1
3
12
Flow temperature, heat circuit. Must be connected
S2
4
12
Return temperature, heat circuit
S3
5
12
Outdoor temperature. Must be connected
S4
6
12
Charging temperature, hot-water circuit. Must be connected
S5
7
12
Return temperature, hot-water circuit
S6
8
12
Upper storage tank temperature. Must be connected
S7
9
12
Lower storage tank temperature. Must be connected
S8
10
12
Default: Room temperature. Can be redefined
S9
11
12
Available
Output Type 1
Name
Pin
Neutral
Description
P1
18
13
Circulation pump, heat circuit
P2
19
13
Charging pump, hot-water circuit
P3
20
13
Circulation pump, hot-water circuit. Can be redefined
M1
16, 17
13
Motor valve on primary side of heat circuit
16: Close. 17: Open
M2
23, 24
13
Motor valve on primary side of heat exchanger in hot-water
circuit. 23: Close. 24: Open
Summary of Contents for ECL 2000