Appendix A. Specifications
EI.65.D4.02
116
A.2 Heat Circuit Settings – Example
Ranges
Heat curve setting
With up to five curve points
Max. limiter
0
→
200 °C
Min. limiter
0
→
200 °C
Neutral zone
0
→
9 K
Integration time
0
→
999 seconds
Proportional band
1
→
99 K
Outdoor dependent return temperature limiter
Curve setting with two points
General limit function
Max or Min
Pump overrun
0
→
9 minutes
Pump/valve motion (once every third day at
stand-by)
ON/OFF
Night setback
10
→
30 °C
Total heating cut-out
ON/OFF
Optimizer boost
0
→
100 %
Optimizer slope time
0
→
200 minutes
Summer cut-out
10
→
30 °C
Closing time at flow limit function
0
→
30 minutes
A.3 Hot Water Circuit Settings – Example
Ranges
Setpoint - Operation at comfort temperature
10
→
99 °C
Setpoint - Operation at night setback tem-
perature
10
→
99 °C
Cut-in difference 1 (lower tank sensor)
0
→
50 K
Cut-in difference 2 (upper tank sensor)
0
→
50 K
Max. time for hot water charging
20
→
200 minutes
Max. time for pump overrun
0
→
9 minutes
Anti-bacteria heat period
0
→
24 hours
Anti-bacteria heat period cut-in time
0:00
→
23:45
Anti-bacteria hot water temperature
1
→
99 °C
Setpoint for return limit temperature
10
→
90 °C
Summary of Contents for ECL 2000
Page 1: ...Installation Guide ECL 2000 11 99 EI 65 D4 02...
Page 2: ......
Page 3: ...Installation Guide ECL 2000 Danfoss A S EI 65 D4 02...
Page 16: ...Mounting EI 65 D4 02 10...
Page 26: ...Electrical Connections EI 65 D4 02 20...
Page 120: ...Application 17 Type 2 Only EI 65 D4 02 114...
Page 134: ...Appendix C Service Menus EI 65 D4 02 128...
Page 136: ...References EI 65 D4 02 130...
Page 140: ...Index EI 65 D4 02 134...