Figure 17. Cable lug and cable gland assembly cross- section
Table 7. Example of the equipment needed for the assembly
Description
Manufacturer's homepage
Art.No./Part No.
Assembly equipment (example)
Torque key and turnkey head
730N/10-50
Key
SE30
Assembly example for a 50 mm
2
cable
Cable with nominal cross-section of 50
mm
2
Radox Elastomer S
Cable lug
10853
Cable gland
P itsch blueglobe TRI bg
225ms tri
Screw
DIN 912 M8x16 (item: 10285)
Washer
DIN 2093, 8,2 x 16 x 0,9 (item:
17332)
Washer
DIN 125 D8 (item: 10285)
Cabling and wiring
Route the power cables as far from the control signal wires as possible. The minimum separating distance is 100 mm. The
crossings must be in an angle of 90º. Power cables and control wires should be routed near the frame of the application.
Make sure that all terminal connections are tightened correctly.
Install the electric device by the instructions. Make sure that all the applications of the system, for
example, batteries are connected to the electric device by the instructions of this user guide and
the product speci c guidelines.