Risk of electric shock if dismounting steps are continued before the electric device is discharged and a safe voltage level
has been measured.
Do not touch the electric device or continue to work with the electric device until it cools down.
Support the electric device during dismounting, handle it with care.
Refer to the Chapter
Dismounting procedure
1. Switch off the electric device.
2. Make sure that the cooling system remains operational.
3. Always measure that no voltage is present on the power terminals before you proceed.
4. Wait until the temperature of the electric device and cooling liquid has decreased below +40 °C.
5. Remove the mounting screws and dismount the electric device from the mounting base.
6. Disconnect the power terminal cabling.
7. Disconnect grounding cables (protective earth).
8. Disconnect the liquid cooling system.
9. Remove the mounting screws and dismount the electric device from the mounting base.
10. Install the connection box lid and other parts and plug all electrical and cooling connections
for longer storage.
11. Lift the electric device off.
Disposal of the electric device
Dispose of the electric device and any of its parts by local laws and regulations.
EC-LTS1200-410
8. Dismounting and disposal of the electric device
| BC355449988603en-000101
©
Danfoss | Produced By: Danfoss Power Solutions | September 2020 | 39