Description

Connector/
channel

Terminal

Board

Remarks

Contact 1: Start/stop

J4/CH 8

32-33

NRCP2-BASE

Used with the remote operating mode (Remote).

Contact 2: Heating/cooling selection

J4/CH 9

63-64

NRCP2-BASE

Used with the remote operating mode (Remote).

Contact 3: Demand limit selection 1

J4/CH 10

73-74

NRCP2-BASE

Customer safety loop input

J4/CH 11A

34-35

NRCP2-BASE

Setpoint selection

J5/CH 13

NRCP2-BASE

Used with the remote operating mode (Remote), unit without NRCP2-SLAVE board.

Contact 3 bis: Demand limit selection 
2

J5/CH 14

NRCP2-BASE

Unit without NRCP2-SLAVE board.

Control, evaporator water pump

J2B/CH 18

NRCP2-BASE

-

Control, condenser water pump

J2B/CH 22

NRCP2-BASE

-

Alarm relay output

J3/CH 24

30A-31A

NRCP2-BASE

-

Unit operation relay output

J3/CH 25

37-38

NRCP2-BASE

This output can be used to use a well pump

CCN network connection

J12

NRCP2-BASE

RS-485 series connection
- Pin 1:
- Pin 2: ground
- Pin 3: signal -

Triac output for boiler command

J2B/CH 20

NRCP2-BASE

-

The following table summarises the connections at the user terminal block.

NRCP2-BASE control board

Optional PD-AUX board

J2A

J2B

J3

J4

J12

J3

3.6.2 - Volt-free contact on/off/cooling/heating

If the unit works in the remote operating mode (Remote) and 

the automatic heating/cooling changeover function is not 

selected and if the user configuration allows this (61WG or 

30WG and Pro-Dialog interface selection) the operation of the 

on/off and the heating/cooling contacts is as follows:

Without multiplexing

Off

On cooling

On heating

On/off contact 

Open

Closed

Closed

Heaing/cooling contact

-

Open

Closed

With multiplexing

Off

On cooling

On heating

On auto

On/off contact 

Open

Closed

Closed

Open

Heaing/cooling contact

Open

Open

Closed

Closed

NOTE: The automatic changeover function (on auto) 
selects the cooling or heating mode based on the outside 
temperature (unit with outside temperature) - see chapter 
5.2).

3.6.3 - Volt-free setpoint selection contact

Cooling

Heating

csp 1

csp 2

hsp 1

hsp 2 

Setpoint selection contact

Open

Closed

Open

Closed

3.6.4 - Volt-free demand limit selection contact

100%

Limit 1

Limit 2

Limit 3

Demand limit 1

Open

Closed

Open

Closed

Demand limit 2

Open

Open

Closed

Closed

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...