Control board

3.2 - Electrical supply to boards

All boards are supplied from a common 24 V a.c. supply 

referred to earth.

CAUTION: Maintain the correct polarity of the power supply 
connection of the boards, to ensure that they are not 
damaged.

In the event of a power supply interrupt, the unit restarts 

automatically without the need for an external command. 

However, any faults active when the supply is interrupted are 

saved and may in certain cases prevent a circuit or unit from 

restarting.

3.3 - Light emitting diodes on boards

All boards continuously check and indicate the proper 

operation of their electronic circuits. A light emitting diode 

(LED) lights on each board when it is operating properly.

•   The red LED that flashes for a two-second period - one 

second on, one second off - indicates correct operation. A 

different rate indicates a board or a software failure.

• 

The green LED flashes continuously on all boards to show 

that the board is communicating correctly over its internal 

bus. If the LED is not flashing, this indicates a LEN bus 

wiring problem.

• 

The orange LED of the master board flashes during any 

communication via the CCN bus.

3.4 - The sensors

Refrigerant pressure sensors

Two types of electronic (high and low-pressure) sensors are 

used to measure the suction and discharge pressure in each 

circuit.

Water system pressure sensors

As an option, two electronic sensors are used to measure the 

suction and the discharge pressure of the water pump. The 

water flow rate is calculated, the unit is protected against water 

flow losses and the pump is protected against cavitation (low 

pump entering pressure).

Thermistors

The water temperature sensors are installed in the entering and 

leaving side. Two optional water temperature sensors can be 

used for master/slave assembly control (in the case of leaving 

water control).

3.5 - The controls

Water circulation pumps

The controller can regulate each water heat exchanger pump and 

takes care of automatic changeover between pumps. Variable-

flow pumps can control the heat exchanger temperature 

difference or the water pressure difference.

Boiler

If there is a unit fault in the heating mode this output authorises 

start-up and shutdown of a boiler.

Immersion heaters

The outputs of the AUX1 board permit control of the electric 

resistance heaters. They are used as a supplementary heating 

source in the heating mode.

3.6 - Connections at the user terminal block

3.6.1 - General description

The contacts below are available at the user terminal block on 

the NRCP2-BASE boards. Some contacts can only be used if 

the unit operates in remote operating type (Remote).

Contrast control 
wheel

Back to the previous 
screen

On/off key

- Unit stopped
- List of available operating 

modes (only in local mode) 

Green  LED

Unit has stopped

Unit starts up

Unit in operation

Red LED

No alarm

Warning

Circuit or complete unit error

Up/Down key

- Navigation
- Modification

Enter key

- Validation
- Selection access

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: