4.9.23 - RESETCFG menu

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

COOLING RESET

oatcr_no

-10 to 51.7

-10

°C

Outside temperature for no reset

oatcr_fu

-10 to 51.7

-10

°C

Outside temperature for maximum reset

dt_cr_no

0 to 13.9

0

^C

Delta T for no reset

dt_cr_fu

0 to 13.9

0

^C

Delta T for maximum reset

cr_deg

-16.7 to 16.7

0

^C

Cooling reset value

HEATING RESET

oathr_no

-10 to 51.7

-10

°C

Outside temperature for no reset

oathr_fu

-10 to 51.7

-10

°C

Outside temperature for maximum reset

dt_hr_no

0 to 13.9

0

^C

Delta T for no reset

dt_hr_fu

0 to 13.9

0

^C

Delta T for maximum reset

hr_deg

-16.7 to 16.7

0

^C

Heating reset value

4.9.24 - USERCONF menu

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

language

 0 to 4

0

-

Language selection  
English = 0, Spanish = 1, French =  2, Portuguese = 3, Italian = 4, 
Translation = 5

use_pass

1 to 9999

11

-

User password

4.9.25 - DATETIME menu

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

hour

0 to 24

hours

Hour

minutes

0 to 59

minutes

Minutes

dow

1 to 7

Day of the week

tom_hol

No/Yes

No

Holiday tomorrow?

tod_hol

No/Yes

No

-

Holiday today

dlig_off

No/Yes

-

Winter time changeover active?

dlig_on

No/Yes

-

Summer time changeover active?

d_of_m

1 to 31

Day of the month

month

1 to 12

Month

year

0 to 99

Year

4.9.26 - Menu CTRL_ID

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

elemt_nb

1 to 239

1

-

Element number

bus_nb

0 to 239

0

-

Bus number

baudrate

9600 to 38400

9600

-

Communication speed

PRO- 30WG

Description

CSA-SR-20H450NN 
-

Software version
Serial number

4.9.27 - OCCx P0xS menu

The control provides three timer programs: schedule 1, 

schedule 2 and schedule 3, that can be activated.

The first timer program (schedule 1) provides a means to 

automatically switch the unit from an occupied mode to an 

unoccupied mode: the unit is started during occupied periods. 

The second timer program (schedule 2) provides a means to 

automatically switch the active setpoint from an occupied 

setpoint to an unoccupied setpoint: cooling setpoint 1 is used 

during occupied periods, cooling or heating setpoint 2 during 

unoccupied periods.

The third timer program (schedule 3) allows the unit to switch 

to the domestic hot water production mode. The DHW mode is 

allowed during occupied periods.

Each schedule consists of eight time periods set by the operator. 

These time periods can be flagged to be in effect or not in effect 

on each day of the week plus a holiday period. The day begins 

at 00.00 hours and ends at 23.59 hours.

Program is in unoccupied mode unless a schedule time period is in 

effect. If two periods overlap and are both active on the same 

day, the occupied mode takes priority over the unoccupied 

period.

Each of the eight periods can be displayed and changed with 

the aid of a sub-sub-menu. The table on page 17 shows how to 

access the period configuration. Method is the same for the time 

schedule 1 or the time schedule 2.

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...