background image

17

5.3 - Heat exchanger water pump control

The unit can control one water pump per heat exchanger. The 

pump is turned on when this option is configured (see 

PUMPCONFIG) and when the unit is in one of the on modes 

described above or in delay mode. Since the minimum value for 

the delay at start-up is 1 minute (configurable between 1 and 15 

minutes), the pump will run for at least one minute before the 

first compressor starts.

The pump is kept running for 2 minutes after the unit goes to stop 

mode. The pump keeps working when the unit switches from 

heating to cooling mode or vice-versa. It is turned off if the unit 

is shut down due to an alarm unless the fault is a frost protection 

error. The pump can be started in particular operating conditions 

when frost protection of the heat exchanger is active (see chapter 

“Control point”). See chapter “Master/slave assembly” for the 

particular heat exchanger pump control for the slave unit 

(master/slave assembly).

If the pump with variable flow option has been selected 

(factory-installed option), it is possible to control the water 

flow in three ways (service parameters):

• 

adjusted fixed flow rate,

• 

constant temperature difference,

• 

constant pressure difference.

In this way it is possible to adjust the water loops and to 

optimise pump operation.

The control provides a means to automatically start the pump 

each day at 14.00 hours for 2 seconds when the unit is off (pump 

anti-stick function). Starting the pump periodically for few 

seconds increases the life-time of the pump bearings and the 

tightness of the pump seal.

5.4 - Control interlock contact

This contact checks the status of a loop (water flow switch and 

customer safety loop, see chapter 3.6). It prevents the unit from 

starting if it is open when the delay at start-up has expired. This 

open contact leads to an alarm shut-down, if the unit is running.

5.5 - Control point

The control point represents the water temperature that the unit 

must produce. The heat exchanger entering water temperature 

is controlled by default, but the heat exchanger leaving water 

temperature can also be controlled (requires a Service 

configuration modification).

Control point = active se reset

5.5.1 - Active setpoint

Three setpoints can be selected as active in cooling mode and 

two in heating mode. Usually, the second setpoint is used for 

unoccupied periods. 

Depending on the current operating type, the active setpoint can 

be selected:

• 

by choosing the item in the GENUNIT menu,

• 

via the user’s volt-free contacts,

• 

via network commands

• 

via the setpoint timer program (schedule 2).

5.2.2 - Heating/cooling/auto selection

The table below summarises the unit heating/cooling opera-tion, 

based on the following parameters:

• 

Control type: indicates whether the unit operates in local, 

remote or CCN mode. See section 5.1.

• 

Unit on/off status: indicates whether the unit is shut down 

(not authorised to start) or in operation (or authorised to 

start).

• 

Heating/cooling/auto selection in local mode: operating 

mode selected via the user interface. See GENUNIT 

menu.

• 

Remote heating/cooling contacts: these contacts are only 

active if the unit is under remote control.

• 

HC_SEL: this network command permits heating/cooling/

auto control, if the unit is in CCN operating mode.

• 

Outside temperature: determines the operation, if the unit 

is in automatic heating/cooling/standby changeover mode.

PARAMETER STATUS
ON/OFF STATUS

CONTROL TYPE

HEATING/COOLING 
SELECTION IN LOCAL 
MODE

REMOTE HEATING/
COOLING CONTACTS

HC_SEL

OUTDOOR TEMPERATURE

OPERATING MODE

Off

-

-

-

-

-

Cooling

On

Local

Cooling

-

-

-

Cooling

On

Local

Heating

-

-

-

Heating

On

Local

Auto

-

-

> Cooling threshold

Cooling

On

Local

Auto

-

-

< Heating threshold

Heating*

On

Local

Auto

-

-

Between cooling and heating thresholds

Standby

On

Remote

-

Cooling mode

-

-

Cooling

On

Remote

-

Heating mode

-

-

Heating

On

Remote

-

Auto mode

-

> Cooling threshold

Cooling

On

Remote

-

Auto mode

-

< Heating threshold

Heating*

On

Remote

-

Auto mode

-

Between cooling and heating thresholds

Standby

On

CCN

-

-

Cooling

-

Cooling

On

CCN

-

-

Heating

-

Heating

On

CCN

-

-

Auto

> Cooling threshold

Cooling

On

CCN

-

-

Auto

< Heating threshold

Heating*

On

CCN

-

-

Auto

Between cooling and heating thresholds

Standby

*  

Does not apply to cooling only units that do not control a boiler.

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: