6.4 - Alarm codes (cont.)

Alarm No. Alarm 

code

Alarm description

Reset type

Probable cause

Action taken by the control

Process faults (cont.)

42

P-30

Communicaiton loss between master 
and slave

Automatic when communication is 
re-established

CCN installation bus defective

Unit goes into autonomous mode

43

P-31

CCN emergency stop

As above

Network command 

As above

44

P-37

Repeated high-pressure unloading, 
circuit A

Automatic

Transducer defective or fan circuit 
fault

None

45

P-38

Repeated high-pressure unloading, 
circuit B

As above

As above

As above

46

P-40

Repeated low suction temperature 
unloading 

Manual

Pressure sensor defective or 
refrigerant charge too low

Circuit is shut down

47

P-41

Repeated low suction temperature 
unloading 

As above

As above

As above

48

P-43

Temperature at heat exchanger too 
low, less than 10°C prevents unit 
start-up

Automatic if the temperature 
detected returns to normal or when 
the mode returns to cooling

Operating compressor protection 
out of range or pressure sensor fault

The unit cannot start

49

MC-nn

Master chiller configuration error 

Automatic when the master 
configuration returns to normal or 
when the unit is no longer in master/
slave mode

Master/slave configuration error

Master/slave mode is stopped

50

FC-n0

No factory configuration

Automatic when the configuration is 
entered

The unit size has not been configured Unit is shut down

51

FC-01

Illegal factory configuration number

Manual

The unit size has been configured 
with the wrong value

As above

52

Sr-00

Maintenance service alert

Manual

The preventive maintenance date 
has passed

53

V3-xx

Fault, variable evaporator water 
pump controller

Automatic

Fault in the variable speed controller Unit is shut down

54

V4-xx

Fault, variable condenser water 
pump controller

As above

As above

As above

55

P62-2

Evaporator water loop control fault, 
missing sensor calibration

Automatic if the calibration is valid

No calibration

As above

P62-3

Water loop control fault, suction 
pressure too low

Automatic the first time, if the water 
system is supplied with water, the 
second time manual if it is the same 
day

Too little water in the system

Unit is shut down

P62-4

Water loop control fault, water pump 
has not started

Manual

Pump fault

As above

P62-5

Reserved

P62-6

Water loop control fault, water pump 
overload

Automatic

Missing pressure head at the water 
pump

Unit is shut down

P62-7

Water loop control fault, water flow 
rate fault

Manual

Serious water leak, pump faulty

Unit is shut down

P62-8

Water loop control fault, water 
pressure sensors mixed up

Automatic

Sensors mixed up

Unit is shut down

56

P61-2

Evaporator water loop control fault, 
missing sensor calibration

Automatic if the calibration is valid

No calibration

As above

P61-3

Water loop control fault, suction 
pressure too low

Automatic the first time, if the water 
system is supplied with water, the 
second time manual if it is the same 
day

Too little water in the system

Unit is shut down

P61-4

Water loop control fault, water pump 
has not started

Manual

Pump fault

As above

P61-5

Reserved

P61-6

Water loop control fault, water pump 
overload

Automatic

Missing pressure head at the water 
pump

Unit is shut down

P61-7

Water loop control fault, water flow 
rate fault

Manual

Serious water leak, pump faulty

Unit is shut down

P61-8

Water loop control fault, water 
pressure sensors mixed up

Automatic

Sensors mixed up

Unit is shut down

57

P-63

High pressure fault in circuit A

Manual

Fan fault

Circuit is shut down 

58

P-64

High pressure fault in circuit B

As above

As above

As above

59

P-97

Reversed evaporator entering/
leaving water sensors

Manual

Sensor defective, sensors reversed

Unit is shut down

60

P-99

Reversed condenser entering/leaving 
water sensors

Manual

Sensor defective, sensors reversed

Unit is shut down

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: