6.4 - Alarm codes (cont.)
Alarm No. Alarm
code
Alarm description
Reset type
Probable cause
Action taken by the control
Process faults (cont.)
42
P-30
Communicaiton loss between master
and slave
Automatic when communication is
re-established
CCN installation bus defective
Unit goes into autonomous mode
43
P-31
CCN emergency stop
As above
Network command
As above
44
P-37
Repeated high-pressure unloading,
circuit A
Automatic
Transducer defective or fan circuit
fault
None
45
P-38
Repeated high-pressure unloading,
circuit B
As above
As above
As above
46
P-40
Repeated low suction temperature
unloading
Manual
Pressure sensor defective or
refrigerant charge too low
Circuit is shut down
47
P-41
Repeated low suction temperature
unloading
As above
As above
As above
48
P-43
Temperature at heat exchanger too
low, less than 10°C prevents unit
start-up
Automatic if the temperature
detected returns to normal or when
the mode returns to cooling
Operating compressor protection
out of range or pressure sensor fault
The unit cannot start
49
MC-nn
Master chiller configuration error
Automatic when the master
configuration returns to normal or
when the unit is no longer in master/
slave mode
Master/slave configuration error
Master/slave mode is stopped
50
FC-n0
No factory configuration
Automatic when the configuration is
entered
The unit size has not been configured Unit is shut down
51
FC-01
Illegal factory configuration number
Manual
The unit size has been configured
with the wrong value
As above
52
Sr-00
Maintenance service alert
Manual
The preventive maintenance date
has passed
53
V3-xx
Fault, variable evaporator water
pump controller
Automatic
Fault in the variable speed controller Unit is shut down
54
V4-xx
Fault, variable condenser water
pump controller
As above
As above
As above
55
P62-2
Evaporator water loop control fault,
missing sensor calibration
Automatic if the calibration is valid
No calibration
As above
P62-3
Water loop control fault, suction
pressure too low
Automatic the first time, if the water
system is supplied with water, the
second time manual if it is the same
day
Too little water in the system
Unit is shut down
P62-4
Water loop control fault, water pump
has not started
Manual
Pump fault
As above
P62-5
Reserved
P62-6
Water loop control fault, water pump
overload
Automatic
Missing pressure head at the water
pump
Unit is shut down
P62-7
Water loop control fault, water flow
rate fault
Manual
Serious water leak, pump faulty
Unit is shut down
P62-8
Water loop control fault, water
pressure sensors mixed up
Automatic
Sensors mixed up
Unit is shut down
56
P61-2
Evaporator water loop control fault,
missing sensor calibration
Automatic if the calibration is valid
No calibration
As above
P61-3
Water loop control fault, suction
pressure too low
Automatic the first time, if the water
system is supplied with water, the
second time manual if it is the same
day
Too little water in the system
Unit is shut down
P61-4
Water loop control fault, water pump
has not started
Manual
Pump fault
As above
P61-5
Reserved
P61-6
Water loop control fault, water pump
overload
Automatic
Missing pressure head at the water
pump
Unit is shut down
P61-7
Water loop control fault, water flow
rate fault
Manual
Serious water leak, pump faulty
Unit is shut down
P61-8
Water loop control fault, water
pressure sensors mixed up
Automatic
Sensors mixed up
Unit is shut down
57
P-63
High pressure fault in circuit A
Manual
Fan fault
Circuit is shut down
58
P-64
High pressure fault in circuit B
As above
As above
As above
59
P-97
Reversed evaporator entering/
leaving water sensors
Manual
Sensor defective, sensors reversed
Unit is shut down
60
P-99
Reversed condenser entering/leaving
water sensors
Manual
Sensor defective, sensors reversed
Unit is shut down