background image

19

5.9 - Control of a boiler

NOTE: The control of the electric heating stages or of a 
boiler is not authorised for slave units.

The unit can control the start-up of a boiler, if it is in heating 

mode. When the boiler is operating, the unit water pump is 

stopped.

The unit and a boiler cannot operate together. In this case the 

boiler output is activated in the following conditions:

• 

The unit is in heating mode, but a fault prevents the use of 

the heat pump capacity.

• 

The unit is in heating mode, but works at a very low 

outdoor temperature, making the heat pump capacity 

insufficient. It is possible to adjust the boiler start-up based 

on the outside temperature (HCCONFIG menu).

5.10 - Master/slave assembly

Two control units can be linked to produce a master/slave 

assembly. The two machines are interconnected over the CCN 

bus. All parameters required for the master/slave function must 

be configured through the Service configura-tion menu.

Master/slave operation requires the connection of a tempe-rature 

probe at the common manifold on each machine, if the heat 

exchanger leaving water temperature is controlled. It is not 

required, if the entering water temperature is controlled.

The master/slave assembly can operate with constant or 

variable flow. In the case of variable flow each machine must 

control its own water pump and automatically shut down the 

pump, if the cooling capacity is zero.

For constant flow operation the pumps for each unit are 

continuously operating, if the system is operating. The master 

unit can control a common pump that will be activated, when 

the system is started. In this case the slave unit pump is not 

used.

All control commands to the master/slave assembly (start/stop, 

setpoint, heating/cooling operation, load shedding, etc.) are 

handled by the unit which is configured as the master, and must 

therefore only be applied to the master unit. They will be 

transmitted automatically to the slave unit.

The master unit can be controlled locally, remotely or by CCN 

com-mands. Therefore to start up the assembly, simply validate 

the Master operating type (Master) on the master unit. If the 

Master has been configured for remote control then use the 

remote volt-free contacts for unit start/stop.

The slave unit must stay in CCN operating type continuously. To 

stop the master/slave assembly, select Local Off on the master 

unit or use the remote volt-free contacts if the unit has been 

configured for remote control.

One of the functions of the master unit (depending on its 

configuration) may be the designation, whether the master or 

slave is to be the lead machine or the follower. The roles of 

lead machine and follower will be reversed when the difference 

in running hours between the two units exceeds a configurable 

value, ensuring that the running times of the two units are 

automatically equalised.

The changeover between lead machine and follower may take 

place when the assembly is started up, or even whilst running. 

The running time balancing function is not active if it has not 

been configured: in this case the lead machine is always the 

master unit.

The lead machine will always be started first. When the lead 

machine is at its full available capacity, start-up delay 

(configurable) is initialised on the follower. When this delay has 

expired, and if the error on the control point is greater than 

1.7°C, the follower unit is authorised to start and the pump is 

activated. The follower will automatically use the master unit 

active setpoint. The lead machine will be held at its full available 

capacity for as long as the active capacity on the follower is not 

zero. When the follower unit receives a command to stop, its 

evaporator water pump is turned off with 20 seconds delay.

In the event of a communication fault between the two units, 

each shall return to an autonomous operating mode until the 

fault is cleared.  If the master unit is halted due to an alarm, the 

slave unit is authorised to start without prior conditions.

ATTENTION: For heat pumps operating in master/slave 
mode and using an NRCP2 board or equipped with electric 
heater stages control must be on the entering water 
temperature.

5.11 - Heating module (HDC) control

61WG units are specially designed to optimise the operation of 

heating installations that require hot-water production for 

traditional heating and domestic hot water (DHW) 

requirements.

In this case an AUX board is included in the unit control box.

The BW10 control system includes algorithms that permit 

constant and automatic optimisation:

• 

control of a three-way directional on/off valve based on 

the heating or domestic hot water requirements

• 

control of the electric heater stages can complement the 

heating loop

• 

hot water setpoint reset (heating application) based on the 

outside air temperature

• 

priority control between heating and domestic hot water 

applications.

5.11.1 – Sensor

An optional outside air temperatrure sensor can be used to reset 

the setpoint or determine the summer/winter mode.

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: