The following tables summarise the possible selections 

depending on the control types (local, remote or network) and 

the following parameters:

• 

Setpoint select in local control: item LSP_SEL in the 

GENUNIT menu permits selection of the active set-point, 

if the unit is in local operating type.

• 

Heating/cooling operating mode.

• 

Setpoint selection contacts: setpoint selection contact 

status.

• 

Schedule 2 status: schedule for setpoint selection.

LOCAL OPERATING MODE

PARAMETER STATUS
Heating/cooling 
operating mode

Local setpoint 
selection

Time schedule 2 
status

Active setpoint

Cooling

sp 1

-

Cooling setpoint 1

Cooling

sp 2

-

Cooling setpoint 2

Cooling

Ice_sp

-

Ice storage cooling 
setpoint

Cooling 

auto

occupied

Cooling setpoint 1

Cooling

auto

unoccupied

Cooling setpoint 2

Heating

sp1

-

Heating setpoint 1

Heating

sp 2 

-

Heating setpoint 2

Heating

sp 3 

-

Heating setpoint 3

Heating

auto

occupied

Heating setpoint 1

Heating

auto

unoccupied

Heating setpoint 2

REMOTE OPERATING MODE

PARAMETER STATUS
Heating/cooling 
operating mode

Setpoint selection 
contact

Active setpoint

Cooling 

sp 1 (open)

Cooling setpoint 1 

Cooling

sp 2 (closed)

Cooling setpoint 2

Heating

sp 1 (open)

Heating setpoint 1

Heating

sp 2 (closed)

Heating setpoint 2

Reset example in cooling mode based on the outside 

temperature

Legend

Maximum reset value

OAT or delta T for no reset

OAT or delta T for full reset

Building Load

5.6 - Capacity control

This function adjusts the number of active compressors to keep 

the heat exchanger water temperature at its setpoint. The 

precision with which this is achieved depends on the capacity 

of the water loop, the flow rate, the load, and the number of 

stages available on the unit. The control system continuously 

takes account of the temperature error with respect to the 

setpoint, as well as the rate of change in this error and the 

difference between entering and leaving water temperatures, in 

order to determine the optimum moment at which to add or 

withdraw a capacity stage.

If the same compressor undergoes too many starts (per hour) or 

runs below one minute each time it is started this automatically 

brings about reduction of compressor starts, which makes 

leaving water temperature control less precise.

The high pressure, low pressure or defrost unloading func-tions 

can also affect temperature control accuracy. Compres-sors are 

started and stopped in a sequence designed to equalise the 

number of start-ups (value weighted by their operating time).

5.7 - Demand limit

The demand limit is used to restrict the unit power consumption. 

The control system allows limitation of the unit capacity, using 

user-controlled volt-free contacts. 

The unit capacity can never exceed the limit setpoint activated 

by these contacts. The limit setpoints can be modified in the 

SETPOINT menu.

5.8 - Night mode

The night period is defined (see GENUNIT configuration) by a 

start time and an end time that are the same for each day of the 

week. During the night period the unit capacity may be limited.

Reset v

alue

Outdoor temperature (OAT)

Heat exchanger delta T

% Building load

5.5.2 - Reset

Reset means that the active setpoint is modified so that the 

machine capacity required is adjusted to be as close as possible 

to the demand. This modification is in general a reaction to a 

drop in the load. For the control system, the source of the reset 

can be configured in the HCCONFIG configuration: it can be 

provided either by the outdoor temperature (that gives a 

measure of the load trends for the building) or by the return 

water temperature (heat exchanger delta T,  gives an average 

building load). 

In response to a drop in the outdoor temperature or to a drop in 

delta T, the cooling setpoint is normally reset upwards in order 

to optimise unit performance: 

In both cases the reset parameters, i.e. slope, source and 

maximum value, are configurable in the RESETCFG menu (see 

section 4.3.8). Reset is a linear function based on three 

parameters.

• 

A reference at which reset is zero (outdoor temperature or 

delta T - no reset value).

• 

A reference at which reset is maximum (outdoor 

temperature or delta T - full reset value).

• 

The maximum reset value.

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...