5.11.2 – Controls

The heating module controls the following elements:

• 

A three-way valve to switch over to domestic hot water 

production

• 

An additional water pump in the heating circuit

• 

Up to four electric heating stages (for supplementary 

safety stage heating)

5.11.3 – User connection terminals

Three volt-free contacts are available at a user connection 

terminal board: 

• 

A contact for DHW demand from the tank

• 

A volt-free contact for DHW priority

• 

A volt-free contact for the summer mode

5.11.4 – Control of additional electric heater stages

The heat pump units can control up to four electric heater 

stages as supplementary heating.

Electric heater stages are activated to supplement the heating 

capacity if the following conditions are satisfied:

• 

The unit uses 100% of its available heating capacity or the 

unit is limited in its operation by a protection mode (e.g. 

low suction temperature protection) and in all cases cannot 

satisfy the heating demand.

• 

The outside temperature is below a configurable threshold 

(see HCCONFIG menu)

• 

Unit demand limitation is not active.

If required the user can configure the last electric heater stage 

available as a safety stage. That safety stage is only activated in 

addition to the other stages, if there is a unit fault that prevents 

the use of the heating capacity. The other electric heater stages 

continue to operate a described above.

The electric heater stages only operate in the heating mode, but 

not during domestc hot water production.

5.11.5 – Heating or domestic hot water

A three-way valve permits switching the heating capacity to a 

heating circuit (fan coil units, radiators or floor heating), or to a 

domestic hot water tank.

The unit requests changeover to the domestic hot water mode if 

all the following conditions have been met:

• 

The volt-free tank request contact is closed AND

• 

Time schedule 3 is in an occupied period OR the volt-free 

priority contact is closed.

Based on the operating mode the water setpoint is adjusted:

• 

In heating mode, setpoints hsp1 and hsp2 are used. They 

can be modified by user reset or based on the outside 

temperature.

• 

In domestic hot water production mode setpoint hsp3 is 

used. No setpoint reset is used.

The unit requests changeover to the heating mode, if at least 

one of the following conditions applies:

• 

The volt-free tank request contact is open OR

• 

The maximum operating duration in the DHW mode has 

finished OR

• 

Time schedule 3 is in an unoccupied period.

If a mode change is requested while a compressor is operat-ing, 

it is stopped before the three-way valve changes to the new 

mode, and then the unit is re-started.

If the unit is in domestic hot water production mode, a “DHW” 

message is displayed on the user interface next to the current 

operating mode. Example: “Local Running DHW”.

5.11.6 – Summer mode

The summer mode is activated when the outside temperature 

exceeds the parameter threshold summ_oat during the summ_

on time. It is deactivated if the outside temperature returns to a 

lower value than the parameter threshold summ_oat during the 

summ_off time. The summer mode can also be activated if the 

volt-free contact SUMM_SW is closed.

5.11.7 – Additonal water pump

An additional water pump, installed in the heating water circuit 

starts if the summer mode is deactivated. If the anti-stick 

function is configured, the additional water pump starts 

periodically.

6 - DIAGNOSTICS - TROUBLESHOOTING

6.1 - General

The control system has many fault tracing aid functions. The 

local interface and its various menus give access to all unit 

operating conditions. If an operating fault is detected, an alarm 

is activated and an alarm code is stored in the Alarms menu, 

sub-menus CUR_ALRM and ALARMRST.

6.2 - Displaying alarms

The alarm LED on the interface (see chapter 4.1) allows the 

quick display of the unit status.

• 

A flashing LED shows that the circuit is operating but 

there is an alert.

• 

A steady LED shows that the circuit has been shut down 

due to a fault.

The ALARMRST menu on the main interface displays up to 

five fault codes that are active on the unit.

6.3 - Resetting alarms

When the cause of the alarm has been corrected the alarm can 

be reset, depending on the type, either automatically on return 

to normal, or manually when action has been taken on the unit. 

Alarms can be reset even if the unit is running.

This means that an alarm can be reset without stopping the 

machine. In the event of a power supply interrupt, the unit 

restarts automatically without the need for an external 

command. However, any faults active when the supply is 

interrupted are saved and may in certain cases prevent a circuit 

or a unit from restarting.

A manual reset must be run from the main interface via the 

ALARMRST menu, item RST_ALM. Depending on the 

configuration in the GENCONF menu, access to the item may 

be protected by a password.

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: