6.4 - Alarm codes
Alarm
No.
Alarm
code
Alarm description
Reset type
Probable cause
Action taken by the control
Thermistor faults
1
th-01
Fluid sensor fault, evaporator water
outlet
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor
Unit is shut down
2
th-02
Fluid sensor fault, evaporator water
inlet
As above
As above
As above
3
th-06
Fluid sensor fault, condenser water
outlet
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor
Unit is shut down
4
th-07
Fluid sensor fault, condenser water
inlet
As above
As above
As above
5
th-10
Outside temperature sensor fault
As above
As above
Unit is shut down
6
th-11
HTWSTEMP fluid sensor fault
(master/slave)
As above
As above
The master/slave mode is
stopped
7
th-12
Suction sensor fault, circuit A
As above
As above
Circuit is shut down
8
th-13
Suction sensor fault, circuit B
As above
As above
As above
9
th-32
CHWSTEMP fluid sensor fault
(master/slave)
As above
As above
The master/slave mode is
stopped
10
th-36
Fluid sensor fault DRY_LWT
As above
As above
Unit is shut down
11
th-44
Sensor fault, discharge circuit A
As above
As above
Circuit is shut down
12
th-45
Sensor fault, discharge circuit B
As above
As above
Circuit is shut down
Pressure transducer faults
13
Pr-01
Discharge pressure transducer fault,
circuit A
Automatic when the voltage transmitted by
the sensor returns to normal
Defective transducer or installation
fault
Circuit is shut down
14
Pr-02
Discharge pressure transducer fault,
circuit B
As above
As above
As above
15
Pr-04
Suction pressure transducer fault,
circuit A
As above
As above
As above
16
Pr-05
Suction pressure transducer fault,
circuit B
As above
As above
As above
17
Pr-24
Entering evaporator water pressure
sensor fault
Automatic when the voltage transmitted by
the sensor returns to normal
Defective transducer or installation
fault
Circuit is shut down
18
Pr-25
Leaving evaporator water pressure
sensor fault
Automatic when the voltage transmitted by
the sensor returns to normal
Defective transducer or installation
fault
Circuit is shut down
19
Pr-26
Entering condenser water pressure
sensor fault
As above
As above
As above
20
Pr-27
Leaving condenser water pressure
sensor fault
As above
As above
As above
Communication with the slave boards
21
CO-BB
Communication loss with the NRCP2
board
Automatic when communication is
re-established
Installation bus fault or defective
slave board
Depending on the configuration,
compressor A3 is shut down or
circuit B is shut down.
22
Co-e1
Communication loss with the EXV
board
As above
As above
Unit is shut down
23
Co-o1
Communication loss with the
PD-AUX 1 board
As above
As above
Unit with optional water pressure
sensors, unit is shut down
24
Co-o2
Communication loss with the
PD-AUX 2 board
As above
As above
Unit with optional water pressure
sensors, unit is shut down
25
Co-o3
Communication loss with the
PD-AUX 3 board
As above
As above
Unit with drycooler, unit is shut
down
26
Co-o4
Communication loss with the
PD-AUX 4 board
As above
As above
Unit with optional electric heater
stages
Process faults
27
P-01
Water heat exchanger frost
protection
Automatic if the same alarm has not tripped
during the last 24 hours, otherwise manual.
Water flow rate too low or defective
thermistor
Unit is shut down
28
P-05
Low suction temperature, circuit A
Automatic when the temperature returns to
normal, and if this alarm has not appeared
during the last 24 hours, otherwise manual.
Pressure sensor defective, EXV
blocked or low refrigerant charge
Circuit is shut down
29
P-06
Low suction temperature, circuit B
As above
As above
As above
30
P-08
High superheat, circuit A
As above
As above
As above
31
P-09
High superheat, circuit B
As above
As above
As above
32
P-11
Low superheat, circuit A
As above
As above
As above
33
P-12
Low superheat, circuit B
As above
As above
As above
34
P-14
Water flow control and customer
interlock fault
Automatic if the unit is in manual shut-down
status, otherwise manual.
Heat exchanger pump defect or
water flow switch fault
Unit is shut down
35
P-15
Condenser water flow control fault
Automatic if the unit is in manual shut-down
status, otherwise manual.
Heat exchanger pump defect or
water flow switch fault
Unit is shut down
36
P-16
Compressor A1 not started or no
pressure increase registered
Manual
Connection problem
Compressor is shut down
37
P-17
Compressor A2 not started or no
pressure increase registered
As above
As above
As above
38
P-18
Compressor A3 not started or no
pressure increase registered
As above
As above
As above
39
P-20
Compressor B1 not started or no
pressure increase registered
As above
As above
As above
40
P-21
Compressor B2 not started or no
pressure increase registered
As above
As above
As above
41
P-29
Communication loss with the System
Manager
Automatic when communication is
re-established
CCN installation bus defective
Unit goes into autonomous mode