21

6.4 - Alarm codes

Alarm 
No.

Alarm 
code

Alarm description

Reset type

Probable cause

Action taken by the control

Thermistor faults

1

th-01

Fluid sensor fault, evaporator water 
outlet

Automatic when the temperature measured 
by the sensor returns to normal

Defective thermistor

Unit is shut down

2

th-02

Fluid sensor fault, evaporator water 
inlet

As above

As above

As above

3

th-06

Fluid sensor fault, condenser water 
outlet

Automatic when the temperature measured 
by the sensor returns to normal

Defective thermistor

Unit is shut down

4

th-07

Fluid sensor fault, condenser water 
inlet

As above

As above

As above

5

th-10

Outside temperature sensor fault

As above

As above

Unit is shut down

6

th-11

HTWSTEMP fluid sensor fault 
(master/slave)

As above

As above

The master/slave mode is 
stopped

7

th-12

Suction sensor fault, circuit A

As above

As above

Circuit is shut down

8

th-13

Suction sensor fault, circuit B

As above

As above

As above

9

th-32

CHWSTEMP fluid sensor fault 
(master/slave)

As above

As above

The master/slave mode is 
stopped

10

th-36

Fluid sensor fault DRY_LWT

As above

As above

Unit is shut down

11

th-44

Sensor fault, discharge circuit A

As above

As above

Circuit is shut down

12

th-45

Sensor fault, discharge circuit B

As above

As above

Circuit is shut down

Pressure transducer faults

13

Pr-01

Discharge pressure transducer fault, 
circuit A

Automatic when the voltage transmitted by 
the sensor returns to normal

Defective transducer or installation 
fault

Circuit is shut down

14

Pr-02

Discharge pressure transducer fault, 
circuit B

As above

As above

As above

15

Pr-04

Suction pressure transducer fault, 
circuit A

As above

As above

As above

16

Pr-05

Suction pressure transducer fault, 
circuit B

As above

As above

As above

17

Pr-24

Entering evaporator water pressure 
sensor fault

Automatic when the voltage transmitted by 
the sensor returns to normal

Defective transducer or installation 
fault

Circuit is shut down

18

Pr-25

Leaving evaporator water pressure 
sensor fault

Automatic when the voltage transmitted by 
the sensor returns to normal

Defective transducer or installation 
fault

Circuit is shut down

19

Pr-26

Entering condenser water pressure 
sensor fault

As above

As above

As above

20

Pr-27

Leaving condenser water pressure 
sensor fault

As above

As above

As above

Communication with the slave boards

21

CO-BB

Communication loss with the NRCP2 
board

Automatic when communication is 
re-established

Installation bus fault or defective 
slave board

Depending on the configuration, 
compressor A3 is shut down or 
circuit B is shut down.

22

Co-e1

Communication loss with the EXV 
board

As above

As above

Unit is shut down

23

Co-o1

Communication loss with the 
PD-AUX 1 board

As above

As above

Unit with optional water pressure 
sensors, unit is shut down

24

Co-o2

Communication loss with the 
PD-AUX 2 board

As above

As above

Unit with optional water pressure 
sensors, unit is shut down

25

Co-o3

Communication loss with the 
PD-AUX 3 board

As above

As above

Unit with drycooler, unit is shut 
down

26

Co-o4

Communication loss with the 
PD-AUX 4 board

As above

As above

Unit with optional electric heater 
stages

Process faults

27

P-01

Water heat exchanger frost 
protection

Automatic if the same alarm has not tripped 
during the last 24 hours, otherwise manual.

Water flow rate too low or defective 
thermistor

Unit is shut down

28

P-05

Low suction temperature, circuit A

Automatic when the temperature returns to 
normal, and if this alarm has not appeared 
during the last 24 hours, otherwise manual.

Pressure sensor defective, EXV 
blocked or low refrigerant charge

Circuit  is shut down

29

P-06

Low suction temperature, circuit B

As above

As above

As above

30

P-08

High superheat, circuit A

As above

As above

As above

31

P-09

High superheat, circuit B

As above

As above

As above

32

P-11

Low superheat, circuit A

As above

As above

As above

33

P-12

Low superheat, circuit B

As above

As above

As above

34

P-14

Water flow control and customer 
interlock fault

Automatic if the unit is in manual shut-down 
status, otherwise manual.

Heat exchanger pump defect or 
water flow switch fault

Unit is shut down

35

P-15

Condenser water flow control fault

Automatic if the unit is in manual shut-down 
status, otherwise manual.

Heat exchanger pump defect or 
water flow switch fault

Unit is shut down

36

P-16

Compressor A1 not started or no 
pressure increase registered

Manual

Connection problem

Compressor is shut down

37

P-17

Compressor A2 not started or no 
pressure increase registered

As above

As above

As above

38

P-18

Compressor A3 not started or no 
pressure increase registered

As above

As above

As above

39

P-20

Compressor B1 not started or no 
pressure increase registered

As above

As above

As above

40

P-21

Compressor B2 not started or no 
pressure increase registered

As above

As above

As above

41

P-29

Communication loss with the System 
Manager

Automatic when communication is 
re-established

CCN installation bus defective

Unit goes into autonomous mode

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: