4.9.8 – HDC_STAT menu 

NAME

FORMAT

UNIT

DESCRIPTION

dhw_mode 

Mode (0 = heating, 1 = DHW, 2 = valve moving)

dhw_dem

No/Yes

-

DHW demand

dhw_time

nnn

mn

DHW mode operating time

shc_time

nnn

mn

Heating mode operating time

sum_mode

No/Yes

-

Summer mode

ctrl_pnt

+-nnn.n

°C

Current setpoint

oat

+-nnn.n

°C

Outside air temperature

DHW_REQ

Open/Close

-

DHW demand volt-free contact (from the tank)

DHW_SW

Open/Close

-

DHW priority volt-free contact

SUMM_SW

Open/Close

-

Summer mode volt-free contact

add_pump

Off/On

-

Additional pump output

dhw_vlv

Off/On

-

DHW three-way valve output

ehs

n

-

Electric heater stages

4.9.9 - RUNTIME menu

NAME

FORMAT

UNIT

DESCRIPTION

hr_mach

nnnnn

hours

Unit operating hours

chr_mach

nnnnn

hours

Unit operating hours in cooling mode

hhr_mach

nnnnn

hours

Unit operating hours in heating mode

st_mach

nnnnn

-

Number of start-ups, unit

HR_CP_A1

nnnnn

hours

Operating hours compressor A1

st_cp_a1

nnnnn

-

Number of start-ups compressor A1

HR_CP_A2

nnnnn

hours

Operating hours compressor A2

st_cp_a2

nnnnn

-

Number of start-ups compressor A2

HR_CP_A3

nnnnn

hours

Operating hours compressor A3

st_cp_a3

nnnnn

-

Number of start-ups compressor A3

HR_CP_B1

nnnnn

hours

Operating hours compressor B1

st_cp_b1

nnnnn

-

Number of start-ups compressor B1

HR_CP_B2

nnnnn

hours

Operating hours compressor B2

st_cp_b2

nnnnn

-

Number of start-ups compressor B2

hr_clpmp

nnnnn

hours

Operating hours evaporator pump

hr_cdpmp

nnnnn

hours

Operating hours condenser pump

Hr_olpmp

nnnnn

-

Operating hours open-loop pump

hr_ehs

nnnnn

-

Operating hours electric heater stages

hr_hdpmp 

nnnnn 

hours

Operating hours HDC module pump 

4.9.10 - MODES menu

NAME

FORMAT

UNIT

DESCRIPTION

m_limit

Yes/No

-

Demand limit active

m_ramp

Yes/No

-

Ramp loading active

m_night

Yes/No

-

Low-noise level night mode

m_SM

Yes/No

-

Aquasmart active

m_leadla

Yes/No

-

Master/slave active

m_auto

Yes/No

-

Changeover active

m_heater

Yes/No

-

Electric heater stages active

m_lo_ewt

Yes/No

-

Lock heating mode and entering water too cold

m_boiler

Yes/No

-

Boiler active

m_sst_a

Yes/No

-

Low suction temperature circuit A

m_sst_b

Yes/No

-

Low suction temperature circuit B

m_dgt_a

Yes/No

-

High discharge gas temperature circuit A

m_dgt_b

Yes/No

-

High discharge gas temperature circuit B

m_hp_a

Yes/No

-

High pressure circuit A

m_hp_b

Yes/No

-

High pressure circuit B

m_sh_a

Yes/No

-

Low superheat circuit A

m_sh_b

Yes/No

-

Low superheat circuit B

m_dhw 

Yes/No

-

Dmomestic hot water mode

m_summer

Yes/No 

-

Summer mode

4.9.11 - ALARMS menu

NAME

DESCRIPTION

ALARMRST

Alarm reset

CUR_ALRM  

Current alarms

ALMHIST1

Alarm history

Summary of Contents for BW10 020-090

Page 1: ...BW10 020 090 Control Operation instructions VMGFU102...

Page 2: ...AL FEATURES 6 4 2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7...

Page 3: ...2 GENERAL DESCRIPTION 2 1 General The BW10 unit has one refrigerant circuit with one or two compressors The unit has an electronic control system to regulate water cooled units with or without hydron...

Page 4: ...ctronic sensors are used to measure the suction and the discharge pressure of the water pump The water flow rate is calculated the unit is protected against water flow losses and the pump is protected...

Page 5: ...lowing table summarises the connections at the user terminal block NRCP2 BASE control board Optional PD AUX board J2A J2B J3 J4 J12 J3 3 6 2 Volt free contact on off cooling heating If the unit works...

Page 6: ...rd entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digi...

Page 7: ...cessible for the first selected character Modify value Description of the screen csp 2 12 0 C Current value 11 5_ C New value before validation Cooling Setpoint 2 Item description The value is validat...

Page 8: ...UMPCONF HCCONFIG RESETCFG USERCONF SCHEDULE HOLIDAY BRODCAST DATETIME CTRL_ID OCC3P03S HCCONFIG HDC_CONF HOLIDY16S HOLIDY02S HOLIDY01S PUMPSTAT HDC_STAT OCC1P01S OCC2P02S 4 8 Menu tree structure NAVIG...

Page 9: ...emperature evaporator HTWSTEMP nnn n C Common master slave temperature condenser DGT A nnn n C Discharge gas temperature A SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suct...

Page 10: ...ibration Following a water pressure sensor error CL_OFFST is deconfigured 99 kPa to inform of the need to calibrate the water loop This calibration must be made while there is no water flow in the mac...

Page 11: ...hours compressor B1 st_cp_b1 nnnnn Number of start ups compressor B1 HR_CP_B2 nnnnn hours Operating hours compressor B2 st_cp_b2 nnnnn Number of start ups compressor B2 hr_clpmp nnnnn hours Operating...

Page 12: ...up to ten a active alarms For each alarm the display shows the time and date the alarm was generated as well as the alarm description Each screen shows one alarm ALARMS CUR_ALM HH MM DD MM YY alarm te...

Page 13: ...No Yes Yes Flow rate verification when the pump has shut down cdpmpseq No Yes No Condenser pump selection cdpmpper No Yes No Condenser pump seizure protection cdpmpsby No Yes No Pump shutdown when the...

Page 14: ...Bus number baudrate 9600 to 38400 9600 Communication speed PRO DIALOG 30WG Description CSA SR 20H450NN Software version Serial number 4 9 27 OCCx P0xS menu The control provides three timer programs s...

Page 15: ...ek MTWTFSSH Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD4 0 00 24 00 00 00 Occupied from UNOCTOD4 0 00 24 00 00 00 Occupied until DOW5 0 1 0 Period 5 days of the week MTWTFS...

Page 16: ...tically on a unit with outside air temperature sensor In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the us...

Page 17: ...ature is controlled by default but the heat exchanger leaving water temperature can also be controlled requires a Service configuration modification Control point active setpoint reset 5 5 1 Active se...

Page 18: ...r withdraw a capacity stage If the same compressor undergoes too many starts per hour or runs below one minute each time it is started this automatically brings about reduction of compressor starts wh...

Page 19: ...ntacts if the unit has been configured for remote control One of the functions of the master unit depending on its configuration may be the designation whether the master or slave is to be the lead ma...

Page 20: ...tank request contact is open OR The maximum operating duration in the DHW mode has finished OR Time schedule 3 is in an unoccupied period If a mode change is requested while a compressor is operat in...

Page 21: ...omatic when communication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 22 Co e1 Communication l...

Page 22: ...ove As above 55 P62 2 Evaporator water loop control fault missing sensor calibration Automatic if the calibration is valid No calibration As above P62 3 Water loop control fault suction pressure too l...

Page 23: ...23...

Page 24: ...VMGFU102...

Reviews: