3.13.4 16-3* Drive Status
Parameters for reporting the status of the frequency converter.
16-30 DC Link Voltage
Range:
Function:
0 V*
[0 - 10000 V]
View a measured value. The value is filtered with an 30 ms time constant.
16-32 Brake Energy /s
Range:
Function:
0.000 kW* [0.000 - 675000.000 kW]
View the brake power transmitted to an external brake resistor, stated as an instantaneous value.
16-33 Brake Energy /2 min
Range:
Function:
0.000 kW* [0.000 - 500.000 kW]
View the brake power transmitted to an external brake resistor. The mean power is calculated on
an average basis for the most recent 120 seconds.
16-34 Heatsink Temp.
Range:
Function:
0 C*
[0 - 255 C]
View the frequency converter heatsink temperature. The cut-out limit is 90 ± 5
°
C, and the motor
cuts back in at 60 ± 5
°
C.
16-35 Inverter Thermal
Range:
Function:
0 %*
[0 - 100 %]
View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
Function:
10.00 A*
[0.01 - 10000.00 A]
View the inverter nominal current, which should match the nameplate data on the connected motor.
The data are used for calculation of torque, motor protection, etc.
16-37 Inv. Max. Current
Range:
Function:
16.00 A*
[0.01 - 10000.00 A]
The current that AKD102 can deliver during 1 min. / 10 min. This value changes depending on
whether it is a high overload or normal overload application. The data are used for calculation of
torque, motor protection, etc.
16-38 SL Controller State
Range:
Function:
0 N/A*
[0 - 100 N/A]
View the state of the event under execution by the SL controller.
16-39 Control Card Temp.
Range:
Function:
0 C*
[0 - 100 C]
View the temperature on the control card, stated in
°
C.
16-40 Logging Buffer Full
Option:
Function:
View whether the logging buffer is full (see par. 15-1*). The logging buffer will never be full when
par.15-13
is set to
Log always
[0].
[0] *
No
[1]
Yes