3-10 Preset Reference
Array [8]
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
Enter up to eight different preset references (0-7) in this parameter, using array programming. The
preset reference is stated as a percentage of the value Ref
MAX
, for
closed loop see par. CL-14
Maximum Reference/Feedb.
). When using preset references, select Pre-
set ref. bit 0 / 1 / 2 [16], [17] or [18] for the corresponding digital inputs in parameter group 5-1*
Digital Inputs.
3-11 Jog Speed [Hz]
Range:
Function:
10.0 Hz*
[0.0 - par. 4-14 Hz]
The jog speed is a fixed output speed at which the frequency converter is running when the jog
function is activated.
See also par.3-80
.
3-13 Reference Site
Option:
Function:
Select which reference site to activate.
[0] *
Linked to Hand / Auto
Use local reference when in Hand mode; or remote reference when in Auto mode.
[1]
Remote
Use remote reference in both Hand mode and Auto mode.
[2]
Local
Use local reference in both Hand mode and Auto mode.
NB!
When set to Local [2], the frequency converter will start with this setting again
following a 'power down'.
3-14 Preset Relative Reference
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
The actual reference, X, is increased or decreased with the percentage Y, set in par.3-14
. This results in the actual reference Z. Actual reference (X) is the sum of the
inputs selected in par.3-15