8-32 Baud Rate
Option:
Function:
Baud rate selection depends on Protocol selection in par. 8-30
Protocol
.
[0]
2400 Baud
[1]
4800 Baud
[2] *
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol par. 8-30
Protocol
using the FC Port. For some of the protocols,
not all options will be visible. Default depends on the protocol selected.
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Function:
10. ms*
[5. - 10000. ms]
Specify the minimum delay time between receiving a request and transmitting a response. This is
used for overcoming modem turnaround delays.
8-36 Maximum Response Delay
Range:
Function:
Application
Depend-
ent*
[11. - 10001. ms]
Specify the maximum permissible delay time between transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause control word time-out.
8-37 Maximum Inter-Char Delay
Range:
Function:
25.00 ms* [0.00 - 35.00 ms]
Specify the maximum permissible time interval between receipt of two bytes. This parameter acti-
vates time-out if transmission is interrupted.
8-40 Telegram Selection
Option:
Function:
Enables use of freely configurable telegrams or standard telegrams for the FC port.
[1] *
Standard telegram 1
[200]
Custom telegram 1
8-45 BTM Transaction Command
Option:
Function:
[0] *
Off
[1]
Start Transaction
[2]
Commit transaction
[3]
Clear error
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
98
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark