3.7.7 5-6* Pulse Outputs
Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated to terminals 27 or 29. Select terminal 27
output in par.5-01
and terminal 29 output in par.5-02
.
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0] *
No operation
Same options and functions as par. 5-6*.
Select the operation variable assigned for terminal 27 readouts.
This parameter cannot be adjusted while the motor is running.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
5-62 Pulse Output Max Freq #27
Range:
Function:
5000 Hz*
[0 - 32000 Hz]
Set the maximum frequency for terminal 27, corresponding to the output variable selected in par.
5-60
Terminal 27 Pulse Output Variable
.
This parameter cannot be adjusted while the motor is running.