[1656]
Feedback 3 [Unit]
View the value of Feedback 3. See also par. 20-0*.
[1660]
Digital Input
Displays the status of the digital inputs. Signal low = 0; Signal high = 1.
Regarding order, see par.16-60
. Bit 0 is at the extreme right.
[1661]
Terminal 53 Switch Setting
Setting of input terminal 53. Current = 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as a reference or protection value.
[1663]
Terminal 54 Switch Setting
Setting of input terminal 54. Current = 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as reference or protection value.
[1665]
Analog Output 42 [mA]
Actual value at output 42 in mA. Use par.6-50
to select the variable to be
represented by output 42.
[1666]
Digital Output [bin]
Binary value of all digital outputs.
[1667]
Pulse Input #29 [Hz]
[1668]
Pulse Input #33 [Hz]
[1669]
Pulse Output #27 [Hz]
Actual value of pulses applied to terminal 27 in digital output mode.
[1670]
Pulse Output #29 [Hz]
Actual value of pulses applied to terminal 29 in digital output mode.
[1671]
Relay Output [bin]
View the setting of all relays.
[1672]
Counter A
View the present value of Counter A.
[1673]
Counter B
View the present value of Counter B.
[1675]
Analog In X30/11
[1676]
Analog In X30/12
[1677]
Analog Out X30/8 [mA]
[1680]
Fieldbus CTW 1
Control word (CTW) received from the Bus Master.
[1682]
Fieldbus REF 1
Main reference value sent with control word via the serial communications network e.g. from the
BMS, PLC or other master controller.
[1684]
Comm. Option STW
Extended fieldbus communication option status word.
[1685]
FC Port CTW 1
Control word (CTW) received from the Bus Master.
[1686]
FC Port REF 1
Status word (STW) sent to the Bus Master.
[1690]
Alarm Word
One or more alarms in a Hex code (used for serial communications)
[1691]
Alarm Word 2
One or more alarms in a Hex code (used for serial communications)
[1692]
Warning Word
One or more warnings in a Hex code (used for serial communications)
[1693]
Warning Word 2
One or more warnings in a Hex code (used for serial communications)
[1694]
Ext. Status Word
One or more status conditions in a Hex code (used for serial communications)
[1695]
Ext. Status Word 2
One or more status conditions in a Hex code (used for serial communications)
[1696]
Maintenance Word
The bits reflect the status for the programmed Preventive Maintenance Events in parameter group
23-1*
[1830]
Analog Input X42/1
Shows the value of the signal applied to terminal X42/1 on the Analog I/O card.
[1831]
Analog Input X42/3
Shows the value of the signal applied to terminal X42/3 on the Analog I/O card.
[1832]
Analog Input X42/5
Shows the value of the signal applied to terminal X42/5 on the Analog I/O card.
[1833]
Analog Out X42/7 [V]
Shows the value of the signal applied to terminal X42/7 on the Analog I/O card.
[1834]
Analog Out X42/9 [V]
Shows the value of the signal applied to terminal X42/9 on the Analog I/O card.
[1835]
Analog Out X42/11 [V]
Shows the value of the signal applied to terminal X42/11 on the Analog I/O card.
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
37