background image

English

2

• Make sure that a separate power supply circuit is provided for this 

unit and that all electrical work is carried out by qualified personnel 
according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical con-
struction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires are used, 

and that there is no strain on the terminal connections or wires.
Improper connections or securing of wires may result in abnormal 
heat build-up or fire.

• When wiring the power supply and connecting the remote control-

ler wiring and transmission wiring, position the wires so that the 
control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric 
shocks, fire or the terminals overheating.

• If refrigerant gas leaks during installation, ventilate the area 

immediately.
Toxic gas may be produced if the refrigerant gas comes into con-
tact with fire.

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the 
room and comes into contact with a source of fire, such as a fan 
heater, stove or cooker.

• Be sure to switch off the unit before touching any electrical parts.
• Do not directly touch refrigerant that has leaked from refrigerant 

pipes or other areas, as there is a danger of frostbite. 

• Do not allow children to climb on the outside unit and avoid plac-

ing objects on the unit. 
Injury may result if the unit becomes loose and falls.

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or tele-
phone earth lead. Imperfect earthing may result in electric shocks 
or fire.
A high surge current from lightning or other sources may cause 
damage to the air conditioner.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric 
shocks or fire.

CAUTION

• While following the instructions in this installation manual, 

install drain piping to ensure proper drainage and insulate pip-
ing to prevent condensation.
Improper drain piping may result in indoor water leakage and 
property damage.

• Install the indoor and outdside units, power cord and connecting 

wires at least 1 meter away from televisions or radios to prevent 
picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter 
may not be sufficient to eliminate noise.)

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent lamps 
(inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as pos-
sible.

• Make sure to provide for adequate measures in order to prevent 

that the outside unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause mal-
functions, smoke or fire. Please instruct the customer to keep the 
area around the unit clean.

• Install in a machine room that is free of moisture.

The unit is designed for indoor use.

• Do not install the air conditioner in the following locations:

1. Where there is a high concentration of mineral oil spray or 

vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leak-
age could result.

2. Where corrosive gas, such as sulphurous acid gas, is pro-

duced.
Corroding of copper pipes or soldered parts may result in 
refrigerant leakage.

3. Near machinery emitting electromagnetic radiation.

Electromagnetic radiation may disturb the operation of the 
control system and result in a malfunction of the unit.

4. Where flammable gas may leak, where there is carbon fibre or 

ignitable dust suspensions in the air, or where volatile flamma-
bles such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.

Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of 
other parts must be done in accordance with relevant local and 
national legislation.

CAUTION

The refrigerant R410A requires that strict precautions be 
observed for keeping the system clean, dry and tightly sealed.
A.Clean and dry

Strict measures must be taken to keep impurities (including 
SUNISO oil and other mineral oils as well as moisture) out of the 
system.

B.Tightly sealed

R410A contains no chlorine, does not destroy the ozone layer 
and so does not reduce the earth’s protection against harmful 
ultraviolet radiation. R410A will contribute only slightly to the 
greenhouse effect if released into the atmosphere. Therefore, 
sealing tightness is particularly important in installation. Care-
fully read the chapter “REFRIGERANT PIPING” and strictly 
observe the correct procedures.

Since design pressure is 4.0 MPa or 40 bar (for R407C units: 
3.3 MPa or 33 bar), the thickness of pipes must be greater than 
previously. Since R410A is a mixed refrigerant, the required addi-
tional refrigerant must be charged in its liquid state. (If the system 
is charged with refrigerant in its gaseous state, due to composi-
tion change, the system will not function normally.) The indoor 
unit is designed for R410A use. See the catalogue for indoor unit 
models that can be connected. (Normal operation is not possible 
when connecting units that are originally designed for other refrig-
erants.)

2.

INTRODUCTION

This installation manual concerns VRV inverters of the Daikin 
RWEYQ-P series. These units are designed for indoor installation 
and used for cooling and heatpump applications.

The RWEYQ-P units can be combined with Daikin VRV series indoor 
units for air conditioning purposes.
The present installation manual describes the procedures for 
unpacking, installing and connecting the RWEYQ-P units. Installa-
tion of the indoor units is not described in this manual. Always refer to 
the installation manual supplied with these units for their installation.

2-1 Combination

The indoor units can be installed in the following range.

Always use appropriate indoor units compatible with R410A.
To lean which models of indoor units are compatible with 
R410A, refer to the product catalogs.

• Total capacity of indoor units

Outside unit

Total capacity index of indoor units

RWEYQ8PY1 ............................. 100 ~ 260
RWEYQ10PY1 ........................... 125 ~ 325
RWEYQ16PY1 ........................... 200 ~ 520
RWEYQ18PY1 ........................... 225 ~ 585
RWEYQ20PY1 ........................... 250 ~ 650
RWEYQ24PY1 ........................... 300 ~ 780
RWEYQ26PY1 ........................... 325 ~ 845
RWEYQ28PY1 ........................... 350 ~ 910
RWEYQ30PY1 ........................... 375 ~ 975

01_EN_3P153897-8L.fm  Page 2  Friday, July 11, 2008  5:04 PM

Summary of Contents for VRV-WIII

Page 1: ...II Manuale di installazione Condizionatore d aria a sistema VRVWIII VRVWIII Installatiehandleiding Airconditioner met VRVWIII Systeem Manual de instala o Ar condicionado VRVWIII System VRVWIII English...

Page 2: ...RXYQ54PY1 E RTSYQ10PY1 RTSYQ14PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24...

Page 3: ...UT D UNIT TO MULTI UNIT IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 8 11 9 10 6 4 Heat recovery system Heat pump system 7 A1P A B...

Page 4: ...OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 figure 16 1 2 3 13 14 15 4 17 16 18 11 10 9 6 5 8 4 7 12 figure 19 figure 18 1 2 6 3 3 4 5 1 2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 14 Heat pump system Heat recovery s...

Page 5: ...t pump system Heat recovery system figure 24 4 5 3 2 1 figure 25 figure 26 1 1 2 2 3 3 4 4 5 6 Heat recovery system Heat pump system figure 23 figure 27 1 2 3 4 5 1 15 2 3 3 C arrow view D arrow view...

Page 6: ...refully before installing air conditioning unit and be sure to install it correctly After completing installation conduct a trial operation to check for faults and explain to the customer how to opera...

Page 7: ...nstall the air conditioner in the following locations 1 Where there is a high concentration of mineral oil spray or vapour e g a kitchen Plastic parts will deteriorate parts may fall off and water lea...

Page 8: ...1 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 2 Consider the space required for refrigerant piping work when insta...

Page 9: ...pipe made of a material other than stainless steel may result in corrosion of the pipe Take preventive measures as necessary for example by insulat ing the connection on the water pipe The connection...

Page 10: ...ce should be activated during operation remove the cause without fail before restarting the operation If the freezing protection device has been once acti vated a partial freezing has occurred If you...

Page 11: ...ntial start refer to chapter Examples For connection wiring to the central remote controller refer to the installation manual of the central remote controller 8 2 Power circuit and cable requirements...

Page 12: ...ge Use insulated wires of the size as mentioned below having rated voltage of 250 V or higher For single core 1 25 mm or larger conduit pipe work For multiple cores 0 75 mm or larger The wiring for pu...

Page 13: ...ution Precautions when laying power wiring Use crimp style terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of differen...

Page 14: ...n 30 against horizontal surface 3 Horizontal surface 7 The outside unit multi connection piping kit that is sold separately as an option BHFP22MA56 84 BHFP26MA56 84 is necessary for the multi installa...

Page 15: ...f outside units See the installation manual attached to the kit with attention to installation restrictions described in connecting the refrigerant piping when installing 1 To avoid the risk of oil de...

Page 16: ...ed to downstream For the gas piping size in case of 2 tube piping between refrigerant branching kit BS unit and refrigerant branching kit select the size of suction gas piping The size of connection p...

Page 17: ...40 m Increase the liquid and suction gas pipe size as follows 9 5 12 7 12 7 15 9 15 9 19 1 19 1 22 2 22 2 25 4 28 6 31 8 34 9 38 1 a A B C D E F G b c d e f g h i j k l m n 1 2 3 4 5 6 7 8 p REFNET jo...

Page 18: ...ING 3 Make sure there is no faulty refrigerant piping See 9 REFRIGERANT PIPING 4 Make sure piping size is correct See 9 1 Selection of piping material 5 Make sure insulation work is done See 9 7 Pipe...

Page 19: ...both liquid and gas is opened See the Shutoff valve operation procedure in chapter 9 10 2 Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the incl...

Page 20: ...supply has been applied For the method of setting refer to the label of Points to be noted when providing ser vices attached to the cover of electrical box shown in the figure 27 of the outside unit A...

Page 21: ...n accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility...

Page 22: ...3P153897 8L EM08A055 0808 HT...

Reviews: