background image

9

English

9.

REFRIGERANT PIPING

Caution

After completing installation, be sure to open the valve. 
(See 

9-9 Additional refrigerant charge

 for details) (Operating 

the unit with the valve shut will break the compressor.)
Use R410A to add refrigerant. 
All field piping must be installed by a licensed refrigeration techni-
cian and must comply with relevant local and national regulations.

CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT 
PIPING

Do not use flux when brazing copper-to copper refrigerant pip-
ing. (Particularly for the HFC refrigerant piping) Therefore, use 
the phosphor copper brazing filler metal (BCuP-2: JIS Z 3264, 
B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping sys-
tems. For instance, if the chlorine based flux is used, it will cause 
pipe corrosion or, in particular, if the flux contains fluorine, it will 
damage the refrigerant oil.)

Note

Installation tools:

Gauge manifold, charge hose, etc.

Make sure to use installation tools that are exclusively used for 
R410A installations to withstand the pressure and to prevent 
foreign materials (e.g. mineral oils such as SUNISO and mois-
ture) from mixing into the system.
(The screw specifications differ for R410A and R407C.)

Vacuum pump

 

1.

Use a 2-stage vacuum pump with a non-return valve.

2.

Make sure the pump oil does not flow oppositely into the sys-
tem while the pump is not working.

3.

Use a vacuum pump which can evacuate to –100.7 kPa (5Torr, 
–755mmHg).

9-1 Selection of piping material

1.

Foreign materials inside pipes (including oils for fabrication) must 
be 30mg/10m or less.

2.

Use the following items for the refrigerant piping.

Material 

: Jointless phosphor-deoxidized copper pipe

Size 

: See 

“Example of connection”

 to determine the correct 

size.

Thickness 

: Select a thickness for the refrigerant piping which 

complies with national and local laws.
For R410A, the design pressure is 4.0 MPa (40-bar).
The minimum thickness of piping according to Japan’s High-
Pressure Gas Safety Law (as of January 2003) is shown 
below.
Temper grade (O type, 1/2H type) in the table indicate the 
material types specified in JIS H 3300.

(unit : mm)

(unit : mm)

3.

Make sure to use the particular branches of piping that have been 
selected referring to chapter “Example of connection”.

4.

Refer to chapter “Shutoff valve operation procedure” in 9-10 about 
the shutoff valve operation procedure.

5.

Make sure to perform the piping installation within the range of the 
maximum allowable pipe length, allowable level difference and 
allowable length after branching as indicated in chapter “Example 
of connection”

6.

For installation of the refrigerant branching kit, refer to the instal-
lation manual delivered with the kit.
And follow the conditions listed below.

Mount the REFNET joint so that it branches either horizontally 
or vertically.

Mount the REFNET header so that it branches horizontally.

(Refer to figure 22)

1.

Horizontal surface

2.

With in 30° against horizontal surface

3.

Horizontal surface

7.

The outside unit multi connection piping kit that is sold separately 
as an option (BHFP22MA56·84, BHFP26MA56·84) is necessary 
for the multi installation of outside units. See the installation man-
ual attached to the kit with attention to the following restrictions 
when installing.

Restriction for the installation of the outside unit multi connec-
tion piping kit

• Install the joint horizontally within a lean of ±15°with caution 

nameplate on top. Refer to figure 23 (Fig. A)
Do not connect it vertically. Refer to figure 23 (Fig. B)

• Reserve the straight part of 500mm or more to the branch pipe 

and do not bend the local pipe in that area.Straight part of 500mm 
or more can be reserved if a local pipe (straight pipe) of 120mm or 
more is connected to the joint. Refer to figure 23 (Fig. C)

• Incorrect installation may cause breakage of outside unit.

(Refer to figure 23)

1.

Caution nameplate

2.

Horizontal line

3.

Ground

4.

Straight part of 500mm or more

5.

Local pipe
(120mm length or more)

9-2 Protection against contamination when 

installing pipes

Take measures to prevent foreign materials like moisture and 
contamination from mixing into the system.

Great caution is needed when passing copper tubes through 
walls.

9-3 Pipe connection

Only use the flare nuts included with the unit.
Using different flare nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or releasing 
nitrogen into the piping will create large quantities of oxidized 
film on the inside of the pipes, adversely affecting valves and 
compressors in the refrigerating system and preventing nor-
mal operation.)

Caution

Do not use anti-oxidants when brazing the pipe joints.
Residue can clog pipes and break equipment.

Note

For nitrogen replacement method,
see the “Installation Manual” (contact your dealer).

• The pressure regulator for the nitrogen released when doing the 

brazing should be set to 0.02 MPa(0.2kg/cm

2

) or less.

(Refer to figure 18)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Nitrogen

4.

Taping

5.

Manual valve

6.

Regulator

Precautions when connecting pipes

• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside 

and outside of the flares and screw them in by hand three or four 
times at first.
(Use ester oil or ether oil.)

• See the following table for tightening torque.

(Applying too much torque may cause the flares to crack.)

• After all the piping has been connected, check the gas leak with 

nitrogen.

Temper grade

O type

outer diameter

φ

6.4

φ

9.5

φ

12.7

φ

15.9

smallest thickness 0.80

0.80

0.80

0.99

Temper grade

1/2H type

outer diameter

φ

19.1

φ

22.2

φ

25.4

φ

28.6

φ

31.8

φ

34.9

φ

38.1

φ

41.3

smallest thickness

0.80

0.80

0.88

0.99

1.10

1.21

1.32

1.43

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the 
period

pipe size

tightening

torque (N · m)

A (mm)

flare shape

φ

9.5

32.7 - 39.9

12.8 - 13.2

φ

12.7

49.5 - 60.3

16.2 - 16.6

φ

15.9

61.8 - 75.4

19.3 - 19.7

R=0.4~0.8

45˚±2

90˚±2

A

01_EN_3P153897-8L.fm  Page 9  Friday, July 11, 2008  5:04 PM

Summary of Contents for VRV-WIII

Page 1: ...II Manuale di installazione Condizionatore d aria a sistema VRVWIII VRVWIII Installatiehandleiding Airconditioner met VRVWIII Systeem Manual de instala o Ar condicionado VRVWIII System VRVWIII English...

Page 2: ...RXYQ54PY1 E RTSYQ10PY1 RTSYQ14PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24...

Page 3: ...UT D UNIT TO MULTI UNIT IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 8 11 9 10 6 4 Heat recovery system Heat pump system 7 A1P A B...

Page 4: ...OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 figure 16 1 2 3 13 14 15 4 17 16 18 11 10 9 6 5 8 4 7 12 figure 19 figure 18 1 2 6 3 3 4 5 1 2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 14 Heat pump system Heat recovery s...

Page 5: ...t pump system Heat recovery system figure 24 4 5 3 2 1 figure 25 figure 26 1 1 2 2 3 3 4 4 5 6 Heat recovery system Heat pump system figure 23 figure 27 1 2 3 4 5 1 15 2 3 3 C arrow view D arrow view...

Page 6: ...refully before installing air conditioning unit and be sure to install it correctly After completing installation conduct a trial operation to check for faults and explain to the customer how to opera...

Page 7: ...nstall the air conditioner in the following locations 1 Where there is a high concentration of mineral oil spray or vapour e g a kitchen Plastic parts will deteriorate parts may fall off and water lea...

Page 8: ...1 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 2 Consider the space required for refrigerant piping work when insta...

Page 9: ...pipe made of a material other than stainless steel may result in corrosion of the pipe Take preventive measures as necessary for example by insulat ing the connection on the water pipe The connection...

Page 10: ...ce should be activated during operation remove the cause without fail before restarting the operation If the freezing protection device has been once acti vated a partial freezing has occurred If you...

Page 11: ...ntial start refer to chapter Examples For connection wiring to the central remote controller refer to the installation manual of the central remote controller 8 2 Power circuit and cable requirements...

Page 12: ...ge Use insulated wires of the size as mentioned below having rated voltage of 250 V or higher For single core 1 25 mm or larger conduit pipe work For multiple cores 0 75 mm or larger The wiring for pu...

Page 13: ...ution Precautions when laying power wiring Use crimp style terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of differen...

Page 14: ...n 30 against horizontal surface 3 Horizontal surface 7 The outside unit multi connection piping kit that is sold separately as an option BHFP22MA56 84 BHFP26MA56 84 is necessary for the multi installa...

Page 15: ...f outside units See the installation manual attached to the kit with attention to installation restrictions described in connecting the refrigerant piping when installing 1 To avoid the risk of oil de...

Page 16: ...ed to downstream For the gas piping size in case of 2 tube piping between refrigerant branching kit BS unit and refrigerant branching kit select the size of suction gas piping The size of connection p...

Page 17: ...40 m Increase the liquid and suction gas pipe size as follows 9 5 12 7 12 7 15 9 15 9 19 1 19 1 22 2 22 2 25 4 28 6 31 8 34 9 38 1 a A B C D E F G b c d e f g h i j k l m n 1 2 3 4 5 6 7 8 p REFNET jo...

Page 18: ...ING 3 Make sure there is no faulty refrigerant piping See 9 REFRIGERANT PIPING 4 Make sure piping size is correct See 9 1 Selection of piping material 5 Make sure insulation work is done See 9 7 Pipe...

Page 19: ...both liquid and gas is opened See the Shutoff valve operation procedure in chapter 9 10 2 Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the incl...

Page 20: ...supply has been applied For the method of setting refer to the label of Points to be noted when providing ser vices attached to the cover of electrical box shown in the figure 27 of the outside unit A...

Page 21: ...n accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility...

Page 22: ...3P153897 8L EM08A055 0808 HT...

Reviews: