background image

3

English

2-2 Standard operation limit

The figures below assume following operating conditions for indoor 
and outside units:

Equivalent pipe length .....................................................7.5m
Level difference ..................................................................0m

Cooling

Heating

A

Inlet water temperature (°C)

B

Indoor temperature (°CWB)

C

Indoor temperature (°CDB)
Range for continuous operation
Range for operation
Range for pull down operation
Range for warming up operation

• Operation range of water volume is 

50-150L/min

The unit is designed for the following operation range:
Water temperature: 20-35°C
Water volume: 60 L/minute or more

• During cooling operation when the outside temperature is very 

low, it is possible that the thermostat switches off automatically in 
order to protect the unit from freezing.

• Hold ambient temperature at 0-40°C

Heat-release from the unit: 0.71 kW/10Hp/hour.
It is therefore recommended to always ventilate the room.

2-3 Standard supplied accessories

• Make sure that the following accessories are included. 

(Check by removing the front panel.)

(Refer to figure 1)

1.

• Operation manual
• Installation manual
• Declaration of conformity
• Clamp  (A)
• Clamp  (B)

2.

• Accessory pipe (1)
• Accessory pipe (2)
• Accessory pipe (3)

Note

The accessory pipe (1), (3) is not used for the heat pump system.

2-4 Option accessory

To install the above outside units, the following optional parts are also 
required.

• Refrigerant branching kit 

(For R410A only: Always use an appropriate kit dedicated for your 
system.)

Heat pump system

Heat recovery system ..... For 3-tube piping

Heat recovery system ..... For 2-tube piping

• Outside unit multi connection piping kit

(For R410A only: Always use an appropriate kit dedicated for 
your system.)

 To select an optimum kit, refer to “

9. REFRIGERANT PIPING

2-5 Technical and electrical specifications

Refer to the Engineering Data Book for the complete list of specifica-
tions.

3.

SELECTION OF LOCATION

This unit does not have specifications for outdoor installation. 
The unit must be installed indoors (example: machine room, …) 
Always install it in a room.
(machine room, etc.)

Paying attention to the conditions mentioned below, select the place 
for installation with a prior approval of customer.

1.

The foundation is strong enough to support the weight of the unit 
and the floor is flat to prevent vibration and noise generation.

2.

Consider the space required for refrigerant piping work when 
installing.  Refer to [Necessary Space].

3.

There is no danger of fire due to leakage of inflammable gas.

4.

The piping length between the outside unit and the indoor unit 
may not exceed the allowable piping length. “

9. REFRIGERANT 

PIPING

”.

5.

Locations where the noise of the unit operating will not disturb 
nearby houses, etc.

6.

Locations with airflow and ventilation holes capable of dissipating 
heat from the machine and where the ambient temperature 
around the outside unit is between 0 and 40°C and the humidity 
does not exceed 80%.

[Necessary Space]

When installing, secure the space mentioned below without fail.

(Refer to figure 2)

1.

In case of a single installation [mm]

2.

In case of series installations [mm]

3.

Top view

4.

Side view

5.

Outside unit

6.

Service Space (front side)

7.

Service Space (back side)

8.

Space for installing water piping

Secure a enough space for removing the front panel.

9.

Ventilation Space

above the area (

) of the outside unit.

10.

Secure spaces in the front, back and top sides as same 
as the case of single installation.

Caution

1.

An inverter air conditioner may cause electronic noise gener-
ated from AM broadcasting. Examine where to install the main 
air conditioner and electric wires, keeping proper distances  
away from stereo equipment, personal computers, etc. 

(Refer to figure 3)

1.

Indoor unit

2.

Branch switch, overcurrent breaker

Name

Accessory pipes

(1)

(2)

(3)

Quantity

1 pc.

1 pc.

1 pc.

Shape

Name

Clamp (A)

Clamp (B)

[Others]

Installation 
manual

Operation
manual

Declaration of 
conformity

Quantity

7 pcs.

2 pcs.

Shape

10

15

20

25

30

35

40

45

15

10

20

25

30

10

15

20

25

30

35

40

45

10

15

20

25

30

A

C

B

(Note)

THIN

THICK

White

Black

REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73H
REFNET joint

KHRP26A22T KHRP26A33T KHRP26A72T KHRP26A73T

REFNET header

KHRP25M33H KHRP25M72H KHRP25M73H

REFNET joint

KHRP25A22T

KHRP25A33T

KHRP25A72T

KHRP25A73T

REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73H
REFNET joint

KHRP26A22T KHRP26A33T KHRP26A72T KHRP26A73T

Number of outside units
connected

2 units

3 units

Heat pump system

BHFP22MA56

BHFP22MA84

Heat recovery system

BHFP26MA56

BHFP26MA84

01_EN_3P153897-8L.fm  Page 3  Friday, July 11, 2008  5:04 PM

Summary of Contents for VRV-WIII

Page 1: ...II Manuale di installazione Condizionatore d aria a sistema VRVWIII VRVWIII Installatiehandleiding Airconditioner met VRVWIII Systeem Manual de instala o Ar condicionado VRVWIII System VRVWIII English...

Page 2: ...RXYQ54PY1 E RTSYQ10PY1 RTSYQ14PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24...

Page 3: ...UT D UNIT TO MULTI UNIT IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 8 11 9 10 6 4 Heat recovery system Heat pump system 7 A1P A B...

Page 4: ...OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 figure 16 1 2 3 13 14 15 4 17 16 18 11 10 9 6 5 8 4 7 12 figure 19 figure 18 1 2 6 3 3 4 5 1 2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 14 Heat pump system Heat recovery s...

Page 5: ...t pump system Heat recovery system figure 24 4 5 3 2 1 figure 25 figure 26 1 1 2 2 3 3 4 4 5 6 Heat recovery system Heat pump system figure 23 figure 27 1 2 3 4 5 1 15 2 3 3 C arrow view D arrow view...

Page 6: ...refully before installing air conditioning unit and be sure to install it correctly After completing installation conduct a trial operation to check for faults and explain to the customer how to opera...

Page 7: ...nstall the air conditioner in the following locations 1 Where there is a high concentration of mineral oil spray or vapour e g a kitchen Plastic parts will deteriorate parts may fall off and water lea...

Page 8: ...1 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 2 Consider the space required for refrigerant piping work when insta...

Page 9: ...pipe made of a material other than stainless steel may result in corrosion of the pipe Take preventive measures as necessary for example by insulat ing the connection on the water pipe The connection...

Page 10: ...ce should be activated during operation remove the cause without fail before restarting the operation If the freezing protection device has been once acti vated a partial freezing has occurred If you...

Page 11: ...ntial start refer to chapter Examples For connection wiring to the central remote controller refer to the installation manual of the central remote controller 8 2 Power circuit and cable requirements...

Page 12: ...ge Use insulated wires of the size as mentioned below having rated voltage of 250 V or higher For single core 1 25 mm or larger conduit pipe work For multiple cores 0 75 mm or larger The wiring for pu...

Page 13: ...ution Precautions when laying power wiring Use crimp style terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of differen...

Page 14: ...n 30 against horizontal surface 3 Horizontal surface 7 The outside unit multi connection piping kit that is sold separately as an option BHFP22MA56 84 BHFP26MA56 84 is necessary for the multi installa...

Page 15: ...f outside units See the installation manual attached to the kit with attention to installation restrictions described in connecting the refrigerant piping when installing 1 To avoid the risk of oil de...

Page 16: ...ed to downstream For the gas piping size in case of 2 tube piping between refrigerant branching kit BS unit and refrigerant branching kit select the size of suction gas piping The size of connection p...

Page 17: ...40 m Increase the liquid and suction gas pipe size as follows 9 5 12 7 12 7 15 9 15 9 19 1 19 1 22 2 22 2 25 4 28 6 31 8 34 9 38 1 a A B C D E F G b c d e f g h i j k l m n 1 2 3 4 5 6 7 8 p REFNET jo...

Page 18: ...ING 3 Make sure there is no faulty refrigerant piping See 9 REFRIGERANT PIPING 4 Make sure piping size is correct See 9 1 Selection of piping material 5 Make sure insulation work is done See 9 7 Pipe...

Page 19: ...both liquid and gas is opened See the Shutoff valve operation procedure in chapter 9 10 2 Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the incl...

Page 20: ...supply has been applied For the method of setting refer to the label of Points to be noted when providing ser vices attached to the cover of electrical box shown in the figure 27 of the outside unit A...

Page 21: ...n accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility...

Page 22: ...3P153897 8L EM08A055 0808 HT...

Reviews: