background image

5

English

5.

Carry out complete cooling/thermal insulation of water piping and 
outdoor dehumidification. If complete cooling or thermal insula-
tion has not been carried out, any damage may be caused during 
severe winter due to freezing, in addition to thermal loss.

6.

When you stop operation during night or winter, it is necessary to 
take measures to prevent water related circuits from natural freez-
ing in the area the ambient temperature drops below 0°C (by water 
drain off, keeping the circulation pump running, warming up by a 
heater, etc.) Freezing of water related circuits may result in any 
damage to the plate type heat exchanger. Therefore, please take 
appropriate measures depending on the circumstances of use.

(Refer to figure 7)

1.

Example of piping

2.

Water inlet piping

3.

Strainer (sold separately as an accessory)

4.

Air discharge plug (for joint use with cleaning port)

5.

Cleaning device

6.

Strainer for pump

7.

Automatic air discharge valve

8.

Water outlet piping

9.

Joint use with water draining plug

10.

Plate type heat exchanger

11.

Outside unit

7-2 Before starting a test run

1.

Before starting a test run, please make sure that the piping work 
has been carried out in a proper manner. Especially, make sure 
that the strainer, air discharge valve, automatic water supply valve, 
expansion tank and cistern are positioned at their places correctly.

2.

After water has been completely filled in, first run the pump only, 
and then make sure that no air has been caught in the water cir-
culation system and the water flow rate is correct. If any air has 
been caught or the flow rate is not enough, the plate type heat 
exchanger may freeze. Measure any water pressure loss before 
and after the outside unit and make sure that the flow rate is as 
designed. In case of any abnormal, stop the test run immediately 
and carry out trouble shooting to resolve the trouble.

3.

Following the installation manual, carry out a test run of the out-
side unit.

4.

After the test run has been completed, inspect the strainer at the 
inlet piping of the outside unit. Clean it if it is dirty.

7-3 Daily service and maintenance

1.

Management of water quality
The plate type heat exchanger has a structure that does not permit 
dismantling and cleaning, or replacing any parts. Please pay  atten-
tion carefully to the quality of water to be used for the plate type 
heat exchanger in order to prevent corrosion and sticking of scale.
The water to be used for the plate type heat exchanger should have 
at least the quality as specified in the table below.
When using any corrosion prevention agent, scale depressant 
agent, etc, such agent should have no corrosive features against 
stainless steel and copper.

2.

Management of chilled water flow rate
If the chilled water flow rate is not enough, it will result in the freez-
ing damage to the plate type heat exchanger. Check for any clog-
ging of the strainer, any air being caught, any reduction in the flow 
rate due to failure of circulation pump by measuring the tempera-
ture and pressure differences at the inlet and outlet ports of the 
plate type heat exchanger. If the aged difference in the tempera-
ture or pressure has increased beyond the proper range, the flow 
rate should have decreased. Stop the operation and remove the 
cause before restarting the operation.

3.

Steps to be taken when a freezing protection device was activated
When the freezing protection device should be activated during 
operation, remove the cause without fail before restarting the 
operation. If the freezing protection device has been once acti-
vated, a partial freezing has occurred. If you restart the operation 
without removing the cause, the plate type heat exchanger will be 
closed and the ice cannot be melted, and in addition, the freezing 
process will be repeated resulting in any damage to the plate type 
heat exchanger, leading to any such accidents that the refrigerant 
starts leaking or water starts entering the refrigerant circuit.

7-4 Water quality

Water quality standards for chilled water, hot water and make-up 
water (4) (6)

[NOTES]
(1) The circle marks in the columns for corrosion or scale to develop.
(2) Corrosion has a tendency to occur when water temperature is 

high (40°C or higher), and if metals with no protective coating 
whatever are directly exposed to water, it would be a good idea to 
take effective measures against corrosion such as adding a cor-
rosion inhibitor or deaeration treatment.

(3) In a condenser water circuit that uses a closed cooling tower, the 

closed circuit circulating water and make-up water must satisfy its 
water quality standards for the hot water system, and passing 
water and make-up water must satisfy those for the circulation 
type cooling water system.

(4) The supply water must be clean tap water, industrial water or 

clean underground water.
Do not use purified or softened water.

(5) The fifteen items in the table above represent typical causes of 

corrosion and scale.

(6) Once through water may cause corrosion. 

Do not use once through water.

7-5 Maintenance of plate type heat exchanger

The performance of a plate type heat exchanger may decline due to 
scale accumulation. It may be damaged by freezing due to the drop 
of flow rate. For this reason, it is necessary to carry out programmed 
maintenances at a regular interval in order to prevent the scale from 
being generated.

1.

Before entering the season for use, carry out the following 
inspections:

1) Conduct a water quality test and make sure that it is within the 

standard.

2) Clean the strainer.
3) Make sure that the flow rate is correct.
4) Make sure that the operational conditions (pressure, flow rate, 

outlet temperature, etc.) are normal.

Item (5)

Cooling water system (3)

Hot water system (2)

Tendency (1)

Circulation  system

Circulation 

water

Make-up

water

Circulation 

water 

(20°C ~ 
60°C)

Make-up

water

Corrosion Scale

Standard items

pH(25°C)

6.5 to 8.2

6.0 to 8.0

7.0 to 8.0

7.0 to 8.0

{

{

Electrical Conductivity

(mS/m)(25°C)

Less than 

80

Less than 

30

Less than 

30

Less than 

30

{

{

Chloride ions 
(mgcl

/L)

Less than 

200

Less than 

50

Less than 

50

Less than 

50

{

Sulfate ions 
(mgSO

4

 

2-

 /L)

Less than 

200

Less than 

50

Less than 

50

Less than 

50

{

Acid consumption

  

(pH4.8)

(mgCaCO

3

/L)

Less than 

100

Less than 

50

Less than 

50

Less than 

50

{

Total hardness 

(mgCaCO

3

/L)

Less than 

200

Less than 

70

Less than 

70

Less than 

70

{

Calcium hardness 

(mgCaCO

3

/L)

Less than 

150

Less than 

50

Less than 

50

Less than 

50

{

Ionic-state silica 
(mgSiO

2

/L)

Less than 

50

Less than 

30

Less than 

30

Less than 

30

{

Reference items

Iron (mgFe/L)

Less than 

1.0

Less than 

0.3

Less than 

1.0

Less than 

0.3

{

{

Copper (mgCu/L)

Less than 

0.3

Less than 

0.1

Less than 

1.0

Less than 

0.1

{

Sulfate ion 
(mgS 

2-

 /L)

Shall not 

be 

detected

Shall not 

be 

detected

Shall not 

be 

detected

Shall not 

be 

detected

{

Ammonium ion 
(mgNH

4

+

/L)

Less than 

1.0

Less than 

0.1

Less than 

0.3

Less than 

0.1

{

Residual chlorine  

(mgCl/L)

Less than 

0.3

Less than 

0.3

Less than 

0.25

Less than 

0.3

{

Free carbon dioxide 

(mgCO

2

/L)

Less than 

4.0

Less than 

4.0

Less than 

0.4

Less than 

4.0

{

Stability index

6.0 to 7.0

{

{

01_EN_3P153897-8L.fm  Page 5  Friday, July 11, 2008  5:04 PM

Summary of Contents for VRV-WIII

Page 1: ...II Manuale di installazione Condizionatore d aria a sistema VRVWIII VRVWIII Installatiehandleiding Airconditioner met VRVWIII Systeem Manual de instala o Ar condicionado VRVWIII System VRVWIII English...

Page 2: ...RXYQ54PY1 E RTSYQ10PY1 RTSYQ14PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24...

Page 3: ...UT D UNIT TO MULTI UNIT IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 8 11 9 10 6 4 Heat recovery system Heat pump system 7 A1P A B...

Page 4: ...OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 figure 16 1 2 3 13 14 15 4 17 16 18 11 10 9 6 5 8 4 7 12 figure 19 figure 18 1 2 6 3 3 4 5 1 2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 14 Heat pump system Heat recovery s...

Page 5: ...t pump system Heat recovery system figure 24 4 5 3 2 1 figure 25 figure 26 1 1 2 2 3 3 4 4 5 6 Heat recovery system Heat pump system figure 23 figure 27 1 2 3 4 5 1 15 2 3 3 C arrow view D arrow view...

Page 6: ...refully before installing air conditioning unit and be sure to install it correctly After completing installation conduct a trial operation to check for faults and explain to the customer how to opera...

Page 7: ...nstall the air conditioner in the following locations 1 Where there is a high concentration of mineral oil spray or vapour e g a kitchen Plastic parts will deteriorate parts may fall off and water lea...

Page 8: ...1 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 2 Consider the space required for refrigerant piping work when insta...

Page 9: ...pipe made of a material other than stainless steel may result in corrosion of the pipe Take preventive measures as necessary for example by insulat ing the connection on the water pipe The connection...

Page 10: ...ce should be activated during operation remove the cause without fail before restarting the operation If the freezing protection device has been once acti vated a partial freezing has occurred If you...

Page 11: ...ntial start refer to chapter Examples For connection wiring to the central remote controller refer to the installation manual of the central remote controller 8 2 Power circuit and cable requirements...

Page 12: ...ge Use insulated wires of the size as mentioned below having rated voltage of 250 V or higher For single core 1 25 mm or larger conduit pipe work For multiple cores 0 75 mm or larger The wiring for pu...

Page 13: ...ution Precautions when laying power wiring Use crimp style terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of differen...

Page 14: ...n 30 against horizontal surface 3 Horizontal surface 7 The outside unit multi connection piping kit that is sold separately as an option BHFP22MA56 84 BHFP26MA56 84 is necessary for the multi installa...

Page 15: ...f outside units See the installation manual attached to the kit with attention to installation restrictions described in connecting the refrigerant piping when installing 1 To avoid the risk of oil de...

Page 16: ...ed to downstream For the gas piping size in case of 2 tube piping between refrigerant branching kit BS unit and refrigerant branching kit select the size of suction gas piping The size of connection p...

Page 17: ...40 m Increase the liquid and suction gas pipe size as follows 9 5 12 7 12 7 15 9 15 9 19 1 19 1 22 2 22 2 25 4 28 6 31 8 34 9 38 1 a A B C D E F G b c d e f g h i j k l m n 1 2 3 4 5 6 7 8 p REFNET jo...

Page 18: ...ING 3 Make sure there is no faulty refrigerant piping See 9 REFRIGERANT PIPING 4 Make sure piping size is correct See 9 1 Selection of piping material 5 Make sure insulation work is done See 9 7 Pipe...

Page 19: ...both liquid and gas is opened See the Shutoff valve operation procedure in chapter 9 10 2 Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the incl...

Page 20: ...supply has been applied For the method of setting refer to the label of Points to be noted when providing ser vices attached to the cover of electrical box shown in the figure 27 of the outside unit A...

Page 21: ...n accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility...

Page 22: ...3P153897 8L EM08A055 0808 HT...

Reviews: