background image

7

English

8-4 Examples

System example (Refer to figure 8)

1.

Field power supply

2.

Main switch

3.

Earth leak detector

4.

Fuse

5.

Cool/heat selector

6.

Remote controller

7.

Outside unit

8.

BS unit

9.

Indoor unit

power supply wiring (sheathed cable)

transmission wiring (sheathed cable)

Caution

• Use a power wire pipe for the power wiring.
• Outside the unit, make sure the weak electric wiring (i.e. for the 

remote controller, transmission, etc.) and the strong electric wir-
ing do not pass near each other, keeping them at least 50 mm 
apart. Proximity may cause electrical interference, malfunctions, 
and breakage.

• Be sure to connect the power wiring to the power wiring terminal 

block and secure it as described in 

Field line connection

.

• Transmission wiring should be secured as described in

 Field line 

connection: transmission wiring and COOL/HEAT selector

.

• Secure the wiring with the accessory clamps so that it does not 

touch the piping.

• Make sure the wiring and the EL. COMPO. BOX cover do not stick 

up above the structure, and close the cover firmly.

Picking power line and transmission line

(Refer to figure 9)

1.

Power supply wiring and wiring for pump operation 
(High voltage)

2.

Connection wiring
(Low voltage)

3.

Set apart

Connect the wire to the terminal block on PC board with care 
since too much pressure may cause breakage of the PC board.
Field line connection: transmission wiring, interlock circuit, 
pump operation output and COOL/HEAT selector

Connect the wire to the terminal block on the PC board with care 
since too much pressure may cause breakage of the PC board.

[In case of single outside unit system]

(Refer to figure 10)

1.

COOL/HEAT selector

2.

Outside unit PC board (A1P)

3.

Take care of the polarity

4.

Use the conductor of sheathed wire (2 wire)(no polarity)

5.

Terminal board (field supply)

6.

Indoor unit

7.

Never connect the power wire.

8.

BS unit A

9.

BS unit B

10.

Last BS unit

11.

Cool-only unit

[In case of multi outside unit system]

(Refer to figure 11)

1.

Unit A (Master unit)

2.

Unit B

3.

Unit C

4.

TO IN/D UNIT

5.

TO OUT/D UNIT

6.

TO MULTI UNIT

7.

To COOL/HEAT selector (only Heat pump system)

8.

To indoor unit

9.

To other systems

• The transmission wiring between the outside units in the same 

pipe line must be connected to the Q1/Q2 (Out Multi) terminals.
Connecting the wires to the (Out-Out) terminals results in system 
malfunction.

• The wiring for the other lines must be connected to the F1/F2 

(Out-Out) terminals of the PC board in the outside unit to which 
the transmission wiring for the indoor units is connected.

• The outside unit to which the transmission wiring for the indoor 

units is connected is master unit.

• The transmission wiring between the outside units must be 30 m 

in length at maximum.

[Setting the interlock circuit and pump operation 
output.]

Pump operation output [high voltage]

• Use insulated wires of the size as mentioned below having rated 

voltage of 250 V or higher:
For single core: 1.25 mm² or larger (conduit pipe work)
For multiple cores: 0.75 mm² or larger

 *The wiring for pump operation output is to be procured locally.

(Refer to figure 12)

1.

Pump operation output terminal (X2M) 
When water pump is linked with system operation, water 
pump operation circuit shall be set between terminals (1) 
and (2).
Contact specification --- 220 VAC, 3mA-0.5A

2.

PC board (A1P)

3.

Mount an insulation sleeve.

4. Connection of interlock circuit

Do not forget to connect an interlock circuit (an auxiliary 
a-contact of electromagnetic switch for the water pump) 
to each outside unit.
(Select without fail an auxiliary a-contact able to switch 
minimum load of DC15V, 1mA.)

When connecting for each outside unit

Connect to the terminal block (X3M) as shown in the bot-
tom right of the sketch.

When connecting multiple outside units as 1 single unit 

(centralized interlock)

For this unit, it is possible to make a centralized interlock 
of multiple outside units using an adapter (sold sepa-
rately as an accessory) for external control of outside 
units.
For details of wiring connection, refer to “

How to cen-

tralized interlock wiring

”.

How to the centralized interlock wiring

• When centralized interlock is done, see (3) “

8-5 In case of a local 

setting

• No wiring to terminal block X3M is necessary when centralized 

interlock is employed

• For multi system, external/external connection wiring shall be 

done for master unit only.

(Refer to figure 13)

1.

Outside unit A

2.

Outside unit B

3.

Outside unit C

4.

Adapter for external control

5.

Interlock circuit of water pump

6.

Out-Out connection wiring

7.

Use the conductor of sheathed wire (2 wire)(no polarity)

[Setting the cool/heat operation type]

1.

Performing cool/heat setting with the remote controller con-
nected to the indoor unit.
Keep the COOL/HEAT selector switch (DS1) on the outside 
unit PC board (A1P) at the factory setting position OFF.

(Refer to figure 16)
1.

 Remote controller

2.

Performing cool/heat setting with the COOL/HEAT selector.
Connect the COOL/HEAT selector (optional) to the A/B/C 
terminals and set the COOL/HEAT selector switch (DS1) on 
the outside unit PC board (A1P) to ON.

(Refer to figure 17)
1.

 COOL/HEAT selector

• For the above wiring, always use sheathed vinyl cords with 0.75 to 

1.25 mm

2

 or cables (2 core wires). (3 core wire are allowable for 

the COOL/HEAT selector only.)

• All transmission wire is field supply.

• If the following limits should be exceeded, be careful that any 

abnormal transmission may be caused;

Maximum wiring length........................1000 m or less
Total wiring length................................2000 m or less
Maximum branching ............................16 branching or less
Wire length between outside unit ........30 m or less

Never connect power supply to any connection wiring and its 
terminal block

, otherwise the entire system may be damaged.

• Up to 16 branches are possible for transmission wiring. However 

no branch is allowed after branch.

(Refer to figure 14)

1.

Branch

2.

Branch after branch

01_EN_3P153897-8L.fm  Page 7  Friday, July 11, 2008  5:04 PM

Summary of Contents for VRV-WIII

Page 1: ...II Manuale di installazione Condizionatore d aria a sistema VRVWIII VRVWIII Installatiehandleiding Airconditioner met VRVWIII Systeem Manual de instala o Ar condicionado VRVWIII System VRVWIII English...

Page 2: ...RXYQ54PY1 E RTSYQ10PY1 RTSYQ14PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24...

Page 3: ...UT D UNIT TO MULTI UNIT IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 IN D OUT D BS F1 F1 F2 F2 F1 F2 8 11 9 10 6 4 Heat recovery system Heat pump system 7 A1P A B...

Page 4: ...OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 figure 16 1 2 3 13 14 15 4 17 16 18 11 10 9 6 5 8 4 7 12 figure 19 figure 18 1 2 6 3 3 4 5 1 2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 14 Heat pump system Heat recovery s...

Page 5: ...t pump system Heat recovery system figure 24 4 5 3 2 1 figure 25 figure 26 1 1 2 2 3 3 4 4 5 6 Heat recovery system Heat pump system figure 23 figure 27 1 2 3 4 5 1 15 2 3 3 C arrow view D arrow view...

Page 6: ...refully before installing air conditioning unit and be sure to install it correctly After completing installation conduct a trial operation to check for faults and explain to the customer how to opera...

Page 7: ...nstall the air conditioner in the following locations 1 Where there is a high concentration of mineral oil spray or vapour e g a kitchen Plastic parts will deteriorate parts may fall off and water lea...

Page 8: ...1 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 2 Consider the space required for refrigerant piping work when insta...

Page 9: ...pipe made of a material other than stainless steel may result in corrosion of the pipe Take preventive measures as necessary for example by insulat ing the connection on the water pipe The connection...

Page 10: ...ce should be activated during operation remove the cause without fail before restarting the operation If the freezing protection device has been once acti vated a partial freezing has occurred If you...

Page 11: ...ntial start refer to chapter Examples For connection wiring to the central remote controller refer to the installation manual of the central remote controller 8 2 Power circuit and cable requirements...

Page 12: ...ge Use insulated wires of the size as mentioned below having rated voltage of 250 V or higher For single core 1 25 mm or larger conduit pipe work For multiple cores 0 75 mm or larger The wiring for pu...

Page 13: ...ution Precautions when laying power wiring Use crimp style terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of differen...

Page 14: ...n 30 against horizontal surface 3 Horizontal surface 7 The outside unit multi connection piping kit that is sold separately as an option BHFP22MA56 84 BHFP26MA56 84 is necessary for the multi installa...

Page 15: ...f outside units See the installation manual attached to the kit with attention to installation restrictions described in connecting the refrigerant piping when installing 1 To avoid the risk of oil de...

Page 16: ...ed to downstream For the gas piping size in case of 2 tube piping between refrigerant branching kit BS unit and refrigerant branching kit select the size of suction gas piping The size of connection p...

Page 17: ...40 m Increase the liquid and suction gas pipe size as follows 9 5 12 7 12 7 15 9 15 9 19 1 19 1 22 2 22 2 25 4 28 6 31 8 34 9 38 1 a A B C D E F G b c d e f g h i j k l m n 1 2 3 4 5 6 7 8 p REFNET jo...

Page 18: ...ING 3 Make sure there is no faulty refrigerant piping See 9 REFRIGERANT PIPING 4 Make sure piping size is correct See 9 1 Selection of piping material 5 Make sure insulation work is done See 9 7 Pipe...

Page 19: ...both liquid and gas is opened See the Shutoff valve operation procedure in chapter 9 10 2 Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the incl...

Page 20: ...supply has been applied For the method of setting refer to the label of Points to be noted when providing ser vices attached to the cover of electrical box shown in the figure 27 of the outside unit A...

Page 21: ...n accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility...

Page 22: ...3P153897 8L EM08A055 0808 HT...

Reviews: