SiUS341802EC
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
178
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
Changing and access the setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds), you can select
the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
To quit and return to the initial status, press the
MODE (BS1)
button.
Changing the value of the selected setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds) you can
select the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
Now the
SET (BS2)
button is used to select the required value of the selected setting.
When the required value is selected, you can define the change of value by pressing the
RETURN (BS3)
button once.
Press the
RETURN (BS3)
button again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor
unit’s fan).
Mode: 2
Setting: 18
Make sure the segment indication is as during normal operation (default situation when shipped
from factory).
Press the
MODE (BS1)
button for over 5 seconds; result segment display:
Press the
SET (BS2)
button 18 times; result segment display:
Press the
RETURN (BS3)
button once; the value which is returned (depending on the actual
field situation), is the status of the setting. In the case of [2-18], default value is "0", which
means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is the current setting situation.
To change the value of the setting, press the
SET (BS2)
button until the required value appears
on the segment indication. When achieved, define the setting value by pressing the
RETURN
(BS3)
button once. To start operation according to the chosen setting, confirm again by
pressing the
RETURN (BS3)
button.
To leave the field setting, press the
MODE (BS1)
button once, you will return to the default
situation when shipped from factory.
By operating the DIP switches it is possible to:
Result: mode 2 accessed.
Result: mode 2 setting 18 is addressed.
Operating the DIP switches
What to do with DIP switch DS1
1
Cool/Heat selector
OFF: Not installed (Factory setting)
2-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2
1-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...