SiUS341802EC
Other Control
Part 4 Functions and Control
108
Reference
8. Other Control
8.1 Backup Operation
If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor unit
from operating, and then conduct emergency operation only with operational compressors or
outdoor units.
Emergency operation with remote controller reset and emergency operation with outdoor unit
PCB setting are available.
(1) Emergency operation with remote controller reset
[Operating method]
Reset the remote controller. (Press the
ON/OFF
button for 4 seconds or more.)
[Details of operation]
Disable the defective outdoor unit from operating temporarily, and then only operate other outdoor
units. (On the system with 1 outdoor unit, this emergency operation is not available.)
(2) Emergency operation with outdoor unit PCB setting
[Setting method]
Make setting of the unit, "the operation of which is to be disabled", in field setting mode (setting
mode 2).
[Details of operation]
Disable the defective outdoor unit from operating, and then only operate other outdoor units.
(On the system with 1 outdoor unit, this emergency operation is not available.)
8.2 Demand Operation
In order to limit the power consumption, the capacity of outdoor unit is forcibly reduced by using
“Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or external
input by external control adaptor for outdoor unit is required.
Refer to page 187 for the power consumption limitation details.
8.3 Heating Operation Prohibition
When outdoor air temperature is too high, outdoor unit cannot operate in heating mode
because:
Low pressure sensor can give pressure value above upper limit of sensor: error
JC
.
Mechanical internal load on compressor increases.
Low compression ratio can result in insufficient compressor internal oil lubrication.
Heating is disabled when outdoor air temperature is above 26°C (78.8°F).
Forced thermostat-OFF on indoor units.
Outdoor fan operates at “step 1”.
Heating operation is enabled when outdoor air temperature drops below 24°C (75.2°F).
Applicable model
Operating method
(1) Emergency operation with
remote controller reset
(Auto backup operation)
(2) Emergency operation with
outdoor unit PCB setting
(Manual backup operation)
RXLQ144-240TA
RXLQ144-240TB
RXYQ192-384TA
Backup operation by outdoor unit Backup operation by outdoor unit
Setting item
Content
Demand 1
The compressor operates at the power of 60-95% or less of the rating.
Demand 2
The compressor operates at the power of 40-55% or less of the rating.
Demand 3
Forced thermostat OFF
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...