SiUS341802EC
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
154
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis
required for reliability.
1 The second code No. 07 is used for disabling the starting of gas furnace interlocking with room
temperature.
1.4.7 Setting of Airflow Rate when Heating
The fan revolution is changed to maintain the sufficient distance for warm air to reach during the
heating operation. The setting should be changed depending on the installation condition of the
unit.
: Factory setting
Note that this setting is effective only during the heating operation.
Second Code No.
Ton
01
02
03
04
05
06
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
Toff
06
0.5°C (0.9°F)
h
h
h
h
h
h
05
0°C (0°F)
h
h
h
h
h
—
04
–0.5°C (–0.9°F)
h
h
h
h
—
—
03
–1°C (–1.8°F)
h
h
h
—
—
—
02
–1.5°C (–2.7°F)
h
h
—
—
—
—
01
–2°C (–3.6°F)
h
—
—
—
—
—
h
—
: Available
: Not available
CXTQ-TA
: Factory setting
Mode
No.
First Code
No.
Symbol
Second Code No.
01
02
03
04
05
06
07 (
1)
11 (21)
1
Ton
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–100°C
(–148°F)
2
Toff
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–1°C
(–1.8°F)
–0.5°C
(–0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
–98°C
(–144.4°F)
Second Code No.
Ton
01
02
03
04
05
06
07
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–100°C
(–148°F)
Toff
07
–98°C (–144.4°F)
—
—
—
—
—
—
h
06
0.5°C (0.9°F)
h
h
h
h
h
h
h
05
0°C (0°F)
h
h
h
h
h
—
h
04
–0.5°C (–0.9°F)
h
h
h
h
—
—
h
03
–1°C (–1.8°F)
h
h
h
—
—
—
h
02
–1.5°C (–2.7°F)
h
h
—
—
—
—
h
01
–2°C (–3.6°F)
h
—
—
—
—
—
h
h
—
: Available
: Not available
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
3
01
Standard
02
Slightly increased
03
Increased
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...