Troubleshooting by Error Code
SiUS341802EC
301
Part 6 Service Diagnosis
3.42 Wet Alarm
Applicable
Models
All outdoor unit models
Error Code
F4
Method of Error
Detection
In cooling operation, detect the condition under which liquid refrigerant returns to the compressor,
according to the temperature and pressure of each part.
Error Decision
Conditions
When the following wet state continues for a period of 90 minutes, an alert is issued.
An error is defined for 120 minutes.
Wet state in outdoor units
When the following wet state continues for a period of 45 minutes, an alert is issued.
Wet state in some of indoor units
Supposed
Causes
Defective suction pipe thermistor
Defective compressor suction thermistor
Defective discharge pipe thermistor
Defective high pressure sensor
Defective indoor unit electronic expansion valve
Dirty air filter
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...