SiUS341802EC
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
196
2.6 Night-Time Low Noise Operation and Demand Operation
2.6.1 Night-Time Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external control
adaptor (optional), you can lower operating noise.
A. When night-time low noise operation is carried out by external contact (with the use of
the external control adaptor for outdoor unit)
.
1. Connect external control adaptor for outdoor unit and short circuit terminal of night-time low
noise operation (Refer below figure). If carrying out demand or low noise input, connect the
adaptor’s terminals as shown below.
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select an external low noise level for the item 2-25.
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If the
condition is set to ON, when the air conditioning load reaches a high level, the low noise
operation command will be ignored to put the system into normal operation mode.)
B. When night-time low noise operation is carried out automatically. (External control
adaptor for outdoor unit is not required.)
1. While in setting mode 2, select a night-time low noise operation level for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation
(i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the starting time as a guide since
it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation
(i.e., 6:00 AM, 7:00 AM, or 8:00 AM) for the item 2-27. (Use the ending time as a guide since it
is estimated according to outdoor air temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If the
condition is set to ON, when the air conditioning load reaches a high level, the system will be put
into normal operation mode even during night-time.)
Setting
Content
Level 1
Set the outdoor fan to Step 6 or lower.
Level 2
Set the outdoor fan to Step 5 or lower.
Level 3
Set the outdoor fan to Step 4 or lower.
Outdoor wiring indicated
by dotted line
External control
adaptor for outdoor unit
Host computer monitor
panel or demand controller
X
X
X
X
X
X
X
X
1
2
3
C
Demand
Low
noise
F1
F2
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...