SiUS341802EC
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
194
Note(s)
In high humid areas, it is recommended to keep this setting to 0 or 1.
[2-89]:
Intermittent fan operation
Default value: 0.
Used for intermittent fan operation to assist snow discharge on outdoor fan.
Value
[2-89]
Intermittent fan
drive setting
Fan speed
Fan OFF time
(min)
Fan ON time
(min)
0 (default)
OFF
—
—
—
1
ON
Low
30
1
2
ON
Medium
30
1
3
ON
Low
15
1
4
ON
Medium
15
1
5
ON
Low
5
1
6
ON
Medium
5
1
7
ON
Low
—
Always ON
[2-90]:
Indoor unit without power
U4
error generation.
In case an indoor unit needs maintenance or repair on the electric side, it is possible to
keep the rest of the
VRV
DX indoor units operating without power supply to some indoor
unit(s).
Default value: 0 (not active)
Field setting 1: Possible to operate system when some indoor units are temporarily
without power supply. Follow the steps below when shutting off power to indoor unit:
(1) Wait 15 minutes after changing setting to 1.
(2) Turn off indoor unit using remote controller and wait 10 minutes before shutting off
power to indoor unit.
If remote controller indicates "Defrost" mode, wait 10 minutes after the "defrost"
indication is cleared from the remote controller before shutting off power to indoor unit.
(3) After finishing maintenance, return power to indoor unit.
(4) Return setting to 0.
Following conditions need to fulfil:
Maximum equivalent piping length of the farthest indoor less than 120 m (394 ft).
Total capacity of powered off indoor units is less than 30% of outdoor unit capacity.
Operation time is limited to 24 hours from when the indoor unit is powered off.
Do not change cooling/heating mode of the system while indoor unit is powered off.
Not possible to use service mode operation (e.g. recovery mode).
Backup operation has priority over this special feature.
[2-92]:
Te target temperature upper limit
Default value: 1.
Value
[2-92]
Te target temperature upper limit
0
L
1 (default)
M
2
H
If Auto Te, then use this setting to address different load profiles. If the frequent operation is at
lower system load, then use a higher setting under [2-92].
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...