Troubleshooting by Error Code
SiUS341802EC
217
Part 6 Service Diagnosis
Note(s)
1
: The system can keep operating, however, be sure to check and repair.
2
: The system may continue operation depending on the conditions.
Outdoor
Unit
H7
l
Outdoor fan motor signal abnormality
Outdoor fan PCB abnormality
H9
l
Outdoor air thermistor (R1T) abnormality
J3
l
Discharge pipe thermistor (R21T) abnormality
Compressor body thermistor (R14T) abnormality
J5
l
Compressor suction thermistor (R12T) abnormality
Suction pipe thermistor (R10T) abnormality
J6
l
Heat exchanger deicer thermistor (R11T) abnormality
Heat exchanger gas pipe thermistor (R8T, R9T) abnormality
J7
l
Receiver inlet thermistor (R3T) abnormality
Subcooling heat exchanger liquid pipe thermistor (R7T) abnormality
Subcooling injection thermistor (R16T) abnormality
J8
l
Heat exchanger liquid pipe thermistor (R4T, R5T) abnormality
Leak detection thermistor (R15T) abnormality
J9
l
Subcooling heat exchanger gas pipe thermistor (R6T) abnormality
Receiver gas purge thermistor (R13T) abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
Inverter PCB abnormality
L2
l
Momentary power failure during test operation
L3
l
Reactor temperature rise abnormality
L4
l
Inverter radiation fin temperature rise abnormality
L5
l
Compressor instantaneous overcurrent
L8
l
Compressor overcurrent
L9
l
Compressor startup abnormality
LC
l
Transmission error between inverter PCB and outdoor unit main PCB
P1
l
Power supply voltage imbalance
P3
l
Reactor surface thermistor abnormality
P4 (
1)
l
Inverter radiation fin temperature abnormality
PJ
l
Field setting abnormality after replacing outdoor unit main PCB or combination of PCB
abnormality
System
U0 (
1)
k
Refrigerant shortage
U1
l
Reverse phase, Open phase
U2
l
Power supply insufficient or instantaneous abnormality
U3
l
Check operation not executed
U4
l
Transmission error between indoor units and outdoor units, Open phase in power
supply wiring
U5
l
Transmission error between remote controller and indoor unit
U7
l
Transmission error between outdoor units
U8
l
Transmission error between main and sub remote controllers
U9
l
Transmission error between indoor units and outdoor units in the same system
UA
l
Improper combination of indoor and outdoor units, indoor units and remote controller
Incorrect gas furnace connecting number
Incorrect electric heater capacity setting
UC (
1)
k
Address duplication of centralized controller
UE
l
Transmission error between centralized controller and indoor unit
UF
l
System not set yet
UH
l
System abnormality, refrigerant system address undefined
Climate Talk communication system combination error (before initial setting for
communication completes)
Climate Talk communication system combination error (after initial setting for
communication completes)
Error
code
Operation
lamp
Error contents
Reference
page
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...