Troubleshooting by Error Code
SiUS341802EC
303
Part 6 Service Diagnosis
Reference
3.43 Refrigerant Overcharged
Applicable
Models
All outdoor unit models
Error Code
F6
Method of Error
Detection
Detect overcharged refrigerant according to outdoor air temperature, heat exchanger deicer
temperature, and liquid pipe temperature during check operation.
Error Decision
Conditions
When the amount of refrigerant, which is calculated using outdoor air temperature, heat exchanger
deicer temperature, and liquid pipe temperature during check operation, exceeds the regular
charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount,
F6
may be displayed on the
remote controller.)
Supposed
Causes
Refrigerant overcharged
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Disconnection of liquid pipe temperature thermistor
Troubleshooting
CHECK 11
Refer to page 380.
Check for the conditions of
mounting of the temperature
sensors of the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor to the piping.
Disconnect the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor from the outdoor
unit main PCB, and then make
measurement of resistance
using a multimeter.
Normal?
Remedy refrigerant overcharging.
YES
NO
NO
Replace the abnormal thermistors,
and then operate the system.
Properly connect the thermistors,
and then operate the system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
CHECK 11
Are the temperature
sensors properly
mounted?
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...