Indoor Unit
SiBE18-821_C
46
Printed Circuit Board Connector Wiring Diagram
3.3
Floor / Ceiling Suspended Dual Type
3.3.1 FLXS25/35/50/60BAVMB
Connectors and
Other Parts
PCB (1): Control PCB
PCB (2): Power Supply PCB
PCB (3): Display PCB
PCB (4): Signal Receiver PCB
1) S6
Connector for swing motor (horizontal swing)
2) S7
Connector for AC fan motor
3) S21
Connector for centralized control (HA)
4) S24
Connector for display PCB
5) S26
Connector for signal receiver PCB
6) S32
Connector for indoor heat exchanger thermistor
7) S37
Connector for power supply PCB
8) JA
Address setting jumper
∗
Refer to page 154 for detail.
JB
Fan speed setting when compressor stops for thermostat OFF
JC
Power failure recovery function
∗
Refer to page 157 for detail.
9) SW2
Select switch for installation (ceiling or floor)
∗
Refer to page 157 for detail.
10) LED A
LED for service monitor (green)
1) S36
Connector for control PCB
2) H1, H2, H3
Connector for terminal board
3) H4, H5, H6
Connector for AC fan motor
4) V1
Varistor
5) FU1
Fuse (3.15 A, 250 V)
1) S25
Connector for control PCB
2) LED1 (H1P)
LED for operation (green)
3) LED2 (H2P)
LED for timer (yellow)
4) LED3 (H3P)
LED for HOME LEAVE operation (red)
1) S27
Connector for control PCB
2) S31 (RTH)
Room temperature thermistor
3) SW1 (S1W)
Forced operation ON/OFF button