Field Settings
Test Operation and Field Settings
159
BRC1E51A7
a
Unit No.
b
First code No.
c
Second code No.
d
Mode
Step
Action
Remote controller
1
Press and hold the [Cancel] button (
)
for 4 seconds to enter the
Field setting
menu.
2
Use the
buttons to select
Field
setting list
and push the [Menu/Enter]
button (
).
3
Use the
buttons to select the desired
Mode
.
4
During group control, when setting by each
indoor unit (
Mode 20, 21, 22
and
23
have
been selected), push the button to
highlight and
buttons to select the
INDOOR UNIT NO. to be set. This
operation is unnecessary when setting by
group.
5
Highlight the second code No. to be
changed using the
buttons, and use
the
buttons to select the desired
second code No.
When setting by group, all of the
second code No. that may be set are
displayed as “*”.
6
Push the [Menu/Enter] button (
) to
display the confirmation screen.
7
Use the
buttons to select
Yes
and push
the [Menu/Enter] button (
).
When multiple setting changes are
needed, repeat steps 3 to 7.
8
Push the [Cancel] button (
) 2 times to
return to basic screen.
a
b
c
d
(R12878)
Field setting
Unit No
Mode
list
Return
Setting
Test operation ON/OFF
Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set
1/2
Return
Field setting
Setting
(R12879)