SiBE18-821_C
Indoor Unit Control (RA Models)
Function
109
7.8
NIGHT SET Mode
Outline
When the OFF timer is set, the NIGHT SET Mode is automatically activated. The NIGHT SET
Mode keeps the airflow rate setting.
Detail
The NIGHT SET Mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers it slightly in
the case of heating. This prevents excessive cooling in summer and excessive heating in winter
to ensure comfortable sleeping conditions, and also conserves electricity.
<Cooling>
Wall Mounted Type E-Series, J-Series, G-Series
Floor Standing Type
Wall Mounted Type F-Series
Floor / Ceiling Suspended Dual Type
Duct Connected Type
<Heating>
(R10870)
TIMER operation
NIGHT SET Circuit ON
Target temperature
+0.5˚C
temperature shift
Operation stops
at the set hours
1 hour
0.5˚C
0.5˚C
0.5˚C
(R14075)
(A) +0.5˚C temperature shift
(B) Target temperature remains the same
Operation stops
at the set hours
1 hour
30 minutes
Target temperature
(A)
(B)
+0.5˚C
temperature shift
TIMER operation
NIGHT SET Mode ON
(A) :
•
When the outdoor temperature is normal and the room
temperature is at the set temperature.
(B) :
•
When the outdoor temperature is high (27˚C or higher).
2˚C
(R10871)
Target temperature
1 hour later
TIMER operation
NIGHT SET Mode ON