Field Settings
SiBE18-821_C
160
Test Operation and Field Settings
Wireless remote
controller
BRC7E530W, BRC7F532F, BRC7EA63W
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
Step
Action
1
Press the [Inspection / Test] button for 4 seconds during normal mode to enter the
field setting mode.
2
Press the [MODE] button to select the desired mode No.
3
Press the [UP] button to select the first code No.
4
Press the [DOWN] button to select the second code No.
5
Press the [RESERVE] button to confirm the setting.
6
Press the [Inspection / Test] button to return to the normal mode.
RESERVE button
[Inspection / Test] button
Mode No.
Field setting mode
UP button
DOWN button
First code No.
Second code No.
MODE button
(R11737)