Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
139
Troubleshooting
Does the error
code "
E9
" recur?
Turn OFF the power supply
once and then turn it ON
again.
Connect properly.
YES
YES
Is
the
electronic
expansion valve
connector X21A or X22A
properly connected to
the outdoor unit
PCB?
NO
NO
Replace the coil of the
electronic expansion valve
(Y1E).
YES
Is
there
difference in
temperature before and
after electronic expansion
valve (Y1E) during
operation?
NO
Mount properly.
YES
Is the
temperature
sensor of each
thermistor (suction
pipe, discharge pipe,
intermediate heat exchanger
and heat exchanger
distributor pipe
thermistors)
mounted
properly?
NO
Replace the coil of the
electronic expansion valve
(Y1E).
Is the coil
resistance of the
electronic expansion
valve normal?
∗
1
NO
YES
A
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution