Troubleshooting by Remote Controller
SiUS281117
Service Diagnosis
177
Check the Thermistors
Thermistors
If the cause of the problem is related to the thermistors, then the thermistors should be checked
prior to changing the PCB.
For more information about these thermistors, see:
Overview of Thermistors
The table below contains an overview of the thermistors:
Indoor
Outdoor
Checking
To check the thermistors, proceed as follows:
CHECK 5
FCQ
FHQ
FAQ
FBQ
FTQ
Thermistor
Table
(on following page)
R1T
R1T
R1T
R1T
—
Suction air thermistor
2
R2T
R2T
R2T
R2T
R1T
Heat exchanger liquid pipe thermistor
2
R3T
R3T
R3T
R3T
R2T
Heat exchanger gas pipe thermistor
2
—
—
—
R4T
—
Discharge air thermistor
3
—
—
—
R5T
—
NTC thermistor
2
RZR18-30
RZQ18-30
RZR36·42
RZQ36·42
Thermistor
Table
(on following page)
R1T
R1T
Outdoor air thermistor
2
R2T
R2T
Discharge pipe thermistor
3
R3T, R5T
R3T, R5T
Suction pipe thermistor
2
R4T
R4T
Heat exchanger thermistor
2
—
R6T
Subcooling heat exchanger thermistor
2
—
R7T
Liquid pipe thermistor
2
R10T
FINTH
Radiation fin thermistor
1
Step
Action
1
Disconnect the thermistor from the PCB
2
Read the temperature and the resistor value.
3
Check if the measured values correspond with the values in the table on the next pages.