SiUS281117
Troubleshooting by Remote Controller
136
Service Diagnosis
Troubleshooting
Is the stop valve open?
NO
YES
Open the stop valve.
Is high
pressure higher than
2.6 MPa at
starting?
Check
and see whether
compressor is short-
circuited or
ground.
NO
YES
Remedy the cause.
YES
Replace the compressor.
Check the installation
conditions.
Replace the compressor.
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.